| Notes |
| Date |
Text |
| 2006-06-01 00:00:00 | | | | | | | NONCOMPLIANT | | | | | | 225.32 LOCATION. | | | THE DISCONNECTING MEANS SHALL BE | | | INSTALLED EITHER INSIDE OR OUTSIDE OF | | | THE BUILDING OR STRUCTURE SERVED OR | | | WHERE THE CONDUCTORS PASS THROUGH THE | | | BUILDING OR STRUCTURE. THE DISCONNECTING | | | MEANS SHALL BE AT A READILY ACCESSIBLE | | | LOCATION NEAREST THE POINT OF ENTRANCE | | | OF THE CONDUCTORS. FOR THE PURPOSES OF | | | THIS SECTION, THE REQUIREMENTS IN 230.6 | | | SHALL BE PERMITTED TO BE UTILIZED. | | | | | | THERE MUST BE A DISCONNECT FROM THE | | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | | GROUPED PER 230.72, SEE THAT ALL | | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | | COMPLIED WITH. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|