 NONCOMPLIANT
  
 225.32 LOCATION.
 THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF
 THE BUILDING OR STRUCTURE SERVED OR
 WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS. FOR THE PURPOSES OF
 THIS SECTION, THE REQUIREMENTS IN 230.6
 SHALL BE PERMITTED TO BE UTILIZED.
  
 THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  