| Plan Review Notes For Permit 06050354 |
| Permit Number |
06050354 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-26 00:00:00 | | | | | | | ******PROVISO****** | | | 1) FBC-2004 424.2.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK. | | | 2) FBC-2004 424.2.14.4 CONNECTIONS, ALL | | | WATER HEATING EQUIPMENT SHALL BE | | | INSTALLED WITH FLANGES OR UNION | | | CONNECTIONS ADJACENT TO THE HEATER. | | | |
|