Plan Review Notes
Plan Review Notes For Permit 06050265
Permit Number 06050265
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-30 00:00:00DENIED;
 SANITARY ISOMETRIC;
 1.BRANCH DRAIN TO AUTOMATIC CLOTHES
 WASHER TO BE 3" FBC-2004 PLUMBING SEC.
 406.3.
 2.LAUNDRY TUB IS REQUIRED DOWN STREAM OF
 THE BATHROOM GROUP. SEC.909.1
 WATER ISOMETRIC;
 1.WATER HAMMER ARRESTORS ARE REQUIRED
 FOR ICE MACHINE, REF. AND HOT SIDE OF
 KITCHEN SINK. PER 604.9 SHOW ON DRAWING
 .
 2.P&T DISCHARGE PIPE CANNOT BE TRAPED
 AND A AIR GAP FITTING IS REQUIRED PER
 SEC. 504.6.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695