| 2006-05-12 00:00:00 | *** DENIED *** |
| | 1)PLEASE SUBMIT A MANUAL J CALCULATION, |
| | PER 2004 FBC 13-607.1.ABC.1 . |
| | |
| | 2) RETURN AIR TRANSFER DUCT TO MASTER |
| | BEDROOM IS TO SMALL, SEE NOTE #8. |
| | |
| | 3) 2ND FLOOR RETURN AIR TRANSFER DUCTS |
| | ARE ALL TO SMALL, SEE NOTE #8. |
| | |
| | 4) PLEASE SUBMIT DETAILED MANUFACTURE'S |
| | SPECIFICATION'S AND INSTALLATION |
| | INSTRUCTIONS FOR GAS FIRE PLACE. |
| | |
| | 5) PLUMBING PLANS PAGE P-4 GAS DIST. IS |
| | SHOWING A GAS DRYER, PLEASE PROVIDE |
| | COMBUSTION AIR IN LAUNDRY-ROOM FOR GAS |
| | DRYER, ON MECHANICAL PLANS PER 2004 |
| | FBC/M 701.1 . |
| | |
| | 6) PLUMBING PLANS PAGE P-4 GAS DIST. IS |
| | SHOWING A GAS BBQ GRILL PLEASE SHOW ON |
| | MECHANICAL PLANS AND SUBMIT DETAILED |
| | MANUFACTURE'S SPECIFICATION'S AND |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 7) PLEASE SHOW ON MECHANICAL PLANS PAGE |
| | M-3 A/C SCHEDULE, EACH SYSTEM'S SENSIBLE |
| | BTU'S. |
| | |
| | 8)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |