Plan Review Notes
Plan Review Notes For Permit 06050265
Permit Number 06050265
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-12 00:00:00*** DENIED ***
 1)PLEASE SUBMIT A MANUAL J CALCULATION,
 PER 2004 FBC 13-607.1.ABC.1 .
  
 2) RETURN AIR TRANSFER DUCT TO MASTER
 BEDROOM IS TO SMALL, SEE NOTE #8.
  
 3) 2ND FLOOR RETURN AIR TRANSFER DUCTS
 ARE ALL TO SMALL, SEE NOTE #8.
  
 4) PLEASE SUBMIT DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR GAS FIRE PLACE.
  
 5) PLUMBING PLANS PAGE P-4 GAS DIST. IS
 SHOWING A GAS DRYER, PLEASE PROVIDE
 COMBUSTION AIR IN LAUNDRY-ROOM FOR GAS
 DRYER, ON MECHANICAL PLANS PER 2004
 FBC/M 701.1 .
  
 6) PLUMBING PLANS PAGE P-4 GAS DIST. IS
 SHOWING A GAS BBQ GRILL PLEASE SHOW ON
 MECHANICAL PLANS AND SUBMIT DETAILED
 MANUFACTURE'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS.
  
 7) PLEASE SHOW ON MECHANICAL PLANS PAGE
 M-3 A/C SCHEDULE, EACH SYSTEM'S SENSIBLE
 BTU'S.
  
 8)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.