| 2006-05-10 00:00:00 | |
| | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PANEL "C" IS NOT LISTED IN PANEL "A". |
| | PLEASE ADD PANEL "C" TO THE SCHEDULE IF |
| | THATS WHERE ITS FED FROM AS THE RISER |
| | INDICATES. |
| | |
| | 2} TO COMPLY WITH ARTICLE 250.52(A)(3), |
| | THE GROUNDING ELECTRODE SYSTEM MUST |
| | INCLUDE FOOTING STEEL. PLEASE INDICATE |
| | SAME ON THE RISER. |
| | |
| | 3} PLEASE SEE CIRCUIT #2/4 OVEN, PANEL |
| | "A". THE OCP@60 AMPS IS TOO LARGE FOR |
| | THE #8 WIRE, 310.16. |
| | |
| | 4} PLEASE SEE 680.70 FOR JACUZZI GFI |
| | REQUIREMENTS AND INDICATE COMPLIANCE ON |
| | PANEL SCHEDULE OR AT THE UNITS. |
| | |
| | 5} THE DINING ROOM RECEPTACLES DO NOT |
| | SHOW A FEED AND NONE ON THE SCHEDULES. |
| | SEE 210.52(B)(1), NO OTHER OUTLETS. |
| | |
| | 6} THE BREAKFAST ROOM IS SHARING A |
| | CIRCUIT WITH THE FAMILY ROOM. SEE |
| | 210.52(B)(1). |
| | |
| | 7} THE CABANA BATH IS ON THE SAME |
| | CIRCUIT WITH THE LAUNDRY, SEE |
| | 210.11(C)(2) AND 210.11(C)(3). |
| | |
| | 8} CIRCUIT A-17 MUST COMPLY WITH |
| | 210.11(C)(3), AND HAVE NO OTHER OUTLETS. |
| | THE RECEPTACLE AT AC#2 IS SHOWN ON THAT |
| | CIRCUIT. |
| | |
| | 9} THE SMOKE DETECTORS ARE REQUIRED TO |
| | BE INTERCONNECTED PER R313.1 RESIDENTIAL |
| | FBC. PLEASE NOTE THEY ARE BEING SHOWN ON |
| | CIRCUITS C-33 AND B-6. VERIFY THEY CAN |
| | BE ON TWO CIRCUITS AND STILL |
| | INTERCONNECT, IF SO PLEASE SUBMIT THAT |
| | SPEC. ALSO ARC FAULT IS REQUIRED ON ALL |
| | BEDROOM "OUTLETS" PER 210.12. NOTE THE |
| | ARTICLE DOES NOT INDICATE THEY MUST BE |
| | ON A BEDROOM CIRCUIT, A SEPERATE ARC |
| | FAULT BREAKER WILL MEET THE INTENT. |
| | |
| | 10} THE FRONT BALCONY RECEPTACLE CANNOT |
| | BE ON WITH THE BATHROOM RECEPTACLES. SEE |
| | B-11, SECOND FLOOR. 210.11(C)(3). |
| | |
| | 11} SEE CIRCUIT B-15, BATH #5, AND |
| | BALCONY OFF BED ROOM #5, RECEPTACLES. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |