| 2006-05-31 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)31.2 WAS CIRCLED ON THE PRODUCT | | | APPROVAL SPECIFICATION.THIS PRESSURE | | | IS TOO LOW FOR 140MPH, FBC TABLE | | | 1609.6B. | | | | | | 2.)INDICATE ON THE PRODUCT APPROVAL OR | | | ON THE INSTALLATION SCHEDULE WHICH | | | CONNECTION TYPE YOU ARE USING AS NOT ALL | | | OF THEM ARE COMPLIANT FOR THE ANCHOR | | | SPACING YOU HAVE SPECIFIED (12"/12"). |
|