| Plan Review Notes For Permit 06050213 |
| Permit Number |
06050213 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2008-02-11 10:59:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** REVISION TO MECHANICAL PLAN ** | | | *** DENIED *** | | | 1) PLEASE SUBMIT A NEW LETTER FROM THE ENGINEER WITH | | | THE JOB ADDRESS AND PERMIT NUMBER 06050213 ON IT. | | | | | | 2) PROVIDE COMBUSTION AIR OR MAKE UP AIR FOR THE GAS | | | WATER HEATER IN THE LAUNDRY ROOM, SEE 2004 FBC/R | | | G2407.1 AND G2407.4. | | | | | | 3) PROVIDE FOR RETURN AIR IN THE NEW MASTER SUITE, SEE | | | 2004 FBC/R M1602.4. | | | | | | 4) SHOW THE CFM'S AT ALL NEW SUPPLY AIR GRILLS ON | | | MECHANICAL PLAN, SEE 2004 WPB AMEND. 106.3.5.4 (10). | | | | | | 5) SHOW WERE THE CLOTHES DRYER VENT WILL TERMINATE AT | | | ON THE MECHANICAL PLAN, SEE 2004 FBC/R M303.4.2. | | | | | | 6) SHOW ANY NEW BATHROOM EXHAUST FANS BEING INSTALLED, | | | ON THE MECHANICALPLAN, SEE 2004 FBC/R R303.3. | | | | | | 7) SHOW THE HEATER KW IN THE A/C EQUIPMENT SCHEDULE, | | | SEE 2004 WPB AMEND. 106.3.5.4 (10). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|