Plan Review Notes
Plan Review Notes For Permit 06050213
Permit Number 06050213
Review Stop M
Sequence Number 6
Notes
Date Text
2008-02-11 10:59:40PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN **
 *** DENIED ***
 1) PLEASE SUBMIT A NEW LETTER FROM THE ENGINEER WITH
 THE JOB ADDRESS AND PERMIT NUMBER 06050213 ON IT.
  
 2) PROVIDE COMBUSTION AIR OR MAKE UP AIR FOR THE GAS
 WATER HEATER IN THE LAUNDRY ROOM, SEE 2004 FBC/R
 G2407.1 AND G2407.4.
  
 3) PROVIDE FOR RETURN AIR IN THE NEW MASTER SUITE, SEE
 2004 FBC/R M1602.4.
  
 4) SHOW THE CFM'S AT ALL NEW SUPPLY AIR GRILLS ON
 MECHANICAL PLAN, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 5) SHOW WERE THE CLOTHES DRYER VENT WILL TERMINATE AT
 ON THE MECHANICAL PLAN, SEE 2004 FBC/R M303.4.2.
  
 6) SHOW ANY NEW BATHROOM EXHAUST FANS BEING INSTALLED,
 ON THE MECHANICALPLAN, SEE 2004 FBC/R R303.3.
  
 7) SHOW THE HEATER KW IN THE A/C EQUIPMENT SCHEDULE,
 SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]