Plan Review Notes
Plan Review Notes For Permit 06050213
Permit Number 06050213
Review Stop P
Sequence Number 4
Notes
Date Text
2006-12-27 09:45:51DENIED 4TH TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE, SEE
 ATTACHED NOTICE FS 553.80(2)(B) REGUARDING FOUR (4)
 TIMES THE FEE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
 NOTE: THE SUBMITTED SANITATY RISER DIAGRAM ON SHEET P-1
 STILL DOES NOT INDICATE ALL TRAP SIZES. PLEASE
 REFERENCE THE CORRECTED SANITARY RISER DIAGRAM IN RED
 ON SHEET P-1 FOR THE RESUBMITTAL.
  
 2. THE WASHING MACHINE DRAIN INDICATED ON SHEET P-1
 SANITARY RISER DIAGRAM IS STILL INDICATED WRONG PER
 FBC-2004 PLUMBING, SECTION 406.3 WASTE CONNECTIONS,
 SECTION 802.4 STAND PIPES, SECTION 708.7 CLEANOUT
 MINIMUM SIZE AND SECTION 708.9 CLEANOUT ACCESS, FOR
 WASHING MACHINE CLEANOUT TO BE INDICATED AT FOUR FEET
 ABOVE FINNISH FLOOR (4' AFF). PLEASE REFERENCE THE
 CORRECTED SANITARY RISER DIAGRAM IN RED ON SHEET P-1
 FOR THE RESUBMITTAL.
  
 3. THE DISHWASHER DRAIN ON SHEET P-1 SANITARY RISER
 DIAGRAM IS STILL INDICATED WRONG PER FBC-2004 PLUMBING,
 SECTION 802.1.6. PLEASE REFERENCE THE CORRECTED
 SANITARY RISER DIAGRAM IN RED ON SHEET P-1 FOR THE
 RESUBMITTAL.
  
 THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE CORRECTED
 TO MEET CODE COMPLIANCE:
  
 4. PLEASE INDICATE ON THE RESUBMITTED DRAWINGS ON
 SHEET P-1 THAT THE WATER-HAMMER ARRESTORS TO BE
 INSTALLED PER FBC-2004 PLUMBING SECTION 604.9.
  
 5. A} SHEET P-2, A TITLE BLOCK IS REQUIRED WITH THE
 FOLLOWING INFORMATION:
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: ITEMS #1 ADDRESS IS DIFFERENT, #2 AND#6 ARE
 MISSING FROM TITLE BLOCK.
 B} REVISED SHEET P-1 RESUBMITTAL IS INTIALED INSTEAD
 OF BEING SIGNED, PLEASE CORRECT THIS ON THE NEXT
 RESUBMITTAL.
  
 6. SHEET P-2 WATER HEATER DETAIL A VACUUM RELIEF VALVE
 IS REQUIRED ON A BOTTOM FED WATER HEATER PER FBC-2004,
 SECTION 504.2. THE HEAT RECOVERY RETURN SHOULD READ
 FUTURE AND IT SHOULD TIE INTO THE C.W. SUPPLY. PLEASE
 REFERENCE THE CORRECTED DETAIL IN RED AND PLEASE
 CORRECT THE WATER HEATER DETAIL TO REFLECT THIS ON THE
 RESUBMITTAL.
  
 7. PER FBC-2004 CHAPTER 1, SECTION 106.1 MINIMUM OF
 TWO COMPLETE SETS OF DRAWINGS ARE REQUIRED, ONLY ONE
 REVISED SHEET P-1 WAS IN THE RESUBMITTAL PACKAGE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  