| 2006-12-27 09:45:51 | DENIED 4TH TIME |
| | REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE, SEE |
| | ATTACHED NOTICE FS 553.80(2)(B) REGUARDING FOUR (4) |
| | TIMES THE FEE: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTION |
| | 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| | FAMILY) SUBMIT A PLUMBING SANITARY |
| | ISOMETRIC RISER DIAGRAM INDICATING ALL |
| | WASTE, VENTS, TRAPS WITH SIZES, AND |
| | CLEANOUT LOCATIONS. |
| | NOTE: THE SUBMITTED SANITATY RISER DIAGRAM ON SHEET P-1 |
| | STILL DOES NOT INDICATE ALL TRAP SIZES. PLEASE |
| | REFERENCE THE CORRECTED SANITARY RISER DIAGRAM IN RED |
| | ON SHEET P-1 FOR THE RESUBMITTAL. |
| | |
| | 2. THE WASHING MACHINE DRAIN INDICATED ON SHEET P-1 |
| | SANITARY RISER DIAGRAM IS STILL INDICATED WRONG PER |
| | FBC-2004 PLUMBING, SECTION 406.3 WASTE CONNECTIONS, |
| | SECTION 802.4 STAND PIPES, SECTION 708.7 CLEANOUT |
| | MINIMUM SIZE AND SECTION 708.9 CLEANOUT ACCESS, FOR |
| | WASHING MACHINE CLEANOUT TO BE INDICATED AT FOUR FEET |
| | ABOVE FINNISH FLOOR (4' AFF). PLEASE REFERENCE THE |
| | CORRECTED SANITARY RISER DIAGRAM IN RED ON SHEET P-1 |
| | FOR THE RESUBMITTAL. |
| | |
| | 3. THE DISHWASHER DRAIN ON SHEET P-1 SANITARY RISER |
| | DIAGRAM IS STILL INDICATED WRONG PER FBC-2004 PLUMBING, |
| | SECTION 802.1.6. PLEASE REFERENCE THE CORRECTED |
| | SANITARY RISER DIAGRAM IN RED ON SHEET P-1 FOR THE |
| | RESUBMITTAL. |
| | |
| | THE FOLLOWING ARE NEW ITEMS THAT NEED TO BE CORRECTED |
| | TO MEET CODE COMPLIANCE: |
| | |
| | 4. PLEASE INDICATE ON THE RESUBMITTED DRAWINGS ON |
| | SHEET P-1 THAT THE WATER-HAMMER ARRESTORS TO BE |
| | INSTALLED PER FBC-2004 PLUMBING SECTION 604.9. |
| | |
| | 5. A} SHEET P-2, A TITLE BLOCK IS REQUIRED WITH THE |
| | FOLLOWING INFORMATION: |
| | FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | NOTE: ITEMS #1 ADDRESS IS DIFFERENT, #2 AND#6 ARE |
| | MISSING FROM TITLE BLOCK. |
| | B} REVISED SHEET P-1 RESUBMITTAL IS INTIALED INSTEAD |
| | OF BEING SIGNED, PLEASE CORRECT THIS ON THE NEXT |
| | RESUBMITTAL. |
| | |
| | 6. SHEET P-2 WATER HEATER DETAIL A VACUUM RELIEF VALVE |
| | IS REQUIRED ON A BOTTOM FED WATER HEATER PER FBC-2004, |
| | SECTION 504.2. THE HEAT RECOVERY RETURN SHOULD READ |
| | FUTURE AND IT SHOULD TIE INTO THE C.W. SUPPLY. PLEASE |
| | REFERENCE THE CORRECTED DETAIL IN RED AND PLEASE |
| | CORRECT THE WATER HEATER DETAIL TO REFLECT THIS ON THE |
| | RESUBMITTAL. |
| | |
| | 7. PER FBC-2004 CHAPTER 1, SECTION 106.1 MINIMUM OF |
| | TWO COMPLETE SETS OF DRAWINGS ARE REQUIRED, ONLY ONE |
| | REVISED SHEET P-1 WAS IN THE RESUBMITTAL PACKAGE. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |