| 2006-12-27 09:54:11 | DENIED 4TH TIME |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED ON THE |
| | RESUBMITTED DRAWINGS TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE REFERENCE PLUMBING COMMENTS NUMBERS 5 AND 7 |
| | FOR THE RESUBMITTAL. |
| | |
| | 2. SHEETS P-1 AND E-1 INDICATE AN ELECTRIC DRYER AND |
| | SHEET P-2 INDICATES A GAS DRYER, THIS IS CONFUSING, |
| | PLEASE CORRELATE THE DRAWINGS ON THE RESUBMITTAL. |
| | PLEASE NOTE IF THERE IS TO BE A GAS DRYER IT ALSO NEEDS |
| | TO BE ADDED TO THE GAS RISER DIAGRAM ON SHEET P-1. |
| | |
| | 3. SHEET P-1 GAS RISER DIAGRAM STATES IN CLOUDED AREA |
| | "APPROXIMATE DISTANCE OF 25' FROM METER TO NEW SERVICE |
| | ENTRANCE" AND THERE APPEARS TO BE A NATURAL GAS METER |
| | INDICATED ON THE RISER DIAGRAM, THIS IS CONFUSING, |
| | PLEASE INDICATE ON THE RESUBMITTED GAS RISER DIAGRAM |
| | ONLY ONE NATURAL GAS METER AND DELETE ALL OTHERS. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |