| Plan Review Notes For Permit 06050213 |
| Permit Number |
06050213 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-16 09:07:04 | *** DENIED *** | | | 1) AS NOTED IN LAST TWO REVIEWS 6-5-06 NOTE #2 AND | | | 9-12-06 NOTE #1 PLEASE CORRECT ENERGY CALCULATIONS, | | | ENERGY CALCULATIONS SHOW 1960 SQ. FT. UNDER AIR, PLANS | | | ARE SHOWING ONLY 1534 SQ. FT. UNDER AIR. | | | | | | 2) AS NOTED IN LAST REVIEW 9-12-06 NOTE #5, SEE PAGE | | | SP-1, D-1, A-1, S-2 ARE SHOWING EXISTING CU-1 CONDENSER | | | UNIT TO REMAIN, WERE PAGE E-1 SHOWS EXIST. CU-1 TO BE | | | REPLACED, PLEASE CORRECT. | | | | | | 3) THEIR ARE NO MANUAL J CALCULATIONS WITH THE PLANS AT | | | THIS TIME. PLEASE SUBMITMANUAL J CALCULATIONS, PER | | | 2004 FBC 13-607.1.ABC.1 . | | | | | | 4) SEE PLANS PAGE M-4 MISSING ENGINEER'S PRINTED NAME | | | MUST APPEAR IN THE TITLE BLOCK, ALSO THE ENGINEERING | | | BUSINESS'S CERTIFICATE OF AUTHORIZATION NUMBER, PER FAC | | | 61G15-23.002 . | | | | | | 5)SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | | TIMES THE FEE. THIS IS ONLY A NOTICE AT THIS TIME. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|