| 2006-11-27 14:29:13 | UNSAT 3RD TIME |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| | LENGTHS INDICATED. |
| | |
| | 2. PLEASE NOTE THAT THE INDICATED MATERIAL ON SHEET P-1 |
| | IS SCH. 40 BLK STEEL PIPE, WITH A TOTAL DEVELOPED |
| | LENGTH OF OVER 30' WHEN ALL CUT SECTIONS OF PIPE ARE |
| | ACCOUNTED FOR AND A TOTAL BTU LOAD OF 96,000 NOT |
| | 121,000 AS THE DRAWING INDICATES. PER FBC-2004 FUEL |
| | GAS, TABLE 402.4 (2)GAS SYSTEM IS SIZED WRONG, PLEASE |
| | REFERENCE THE CORRECTED GAS RISER AND TOTAL BTU LOAD IN |
| | RED FOR THE RESUBMITTAL. |
| | |
| | 3. PER FBC-2004 FUEL GAS SECTION 404.11 PIPING |
| | UNDERGROUND BENEATH BILDING. PLEASE PROVIDE A DETAIL OF |
| | THIS INSTALLATION. |
| | NOTE: AS AN ALTERNATIVE IT IS SUGGESTED TO PIPE GAS |
| | OVERHEAD INSTEAD OF UNDERGROUND. |
| | |
| | 4. PLEASE INDICATE ON THE RESUBMITTAL COMPLIANCE WITH |
| | FBC-2004 FUEL GAS, SECTIONS 404.8 AND 404.8.1 |
| | PROTECTION AGAINST CORROSION. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |