2006-11-27 14:29:13UNSAT 3RD TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED.
  
 2. PLEASE NOTE THAT THE INDICATED MATERIAL ON SHEET P-1
 IS SCH. 40 BLK STEEL PIPE, WITH A TOTAL DEVELOPED
 LENGTH OF OVER 30' WHEN ALL CUT SECTIONS OF PIPE ARE
 ACCOUNTED FOR AND A TOTAL BTU LOAD OF 96,000 NOT
 121,000 AS THE DRAWING INDICATES. PER FBC-2004 FUEL
 GAS, TABLE 402.4 (2)GAS SYSTEM IS SIZED WRONG, PLEASE
 REFERENCE THE CORRECTED GAS RISER AND TOTAL BTU LOAD IN
 RED FOR THE RESUBMITTAL.
  
 3. PER FBC-2004 FUEL GAS SECTION 404.11 PIPING
 UNDERGROUND BENEATH BILDING. PLEASE PROVIDE A DETAIL OF
 THIS INSTALLATION.
 NOTE: AS AN ALTERNATIVE IT IS SUGGESTED TO PIPE GAS
 OVERHEAD INSTEAD OF UNDERGROUND.
  
 4. PLEASE INDICATE ON THE RESUBMITTAL COMPLIANCE WITH
 FBC-2004 FUEL GAS, SECTIONS 404.8 AND 404.8.1
 PROTECTION AGAINST CORROSION.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  