Plan Review Notes
Plan Review Notes For Permit 06050213
Permit Number 06050213
Review Stop M
Sequence Number 2
Notes
Date Text
2006-09-12 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-5-06 #2.
 PLEASE MAKE CORRECTIONS TO ENERGY
 CALCULATIONS, SEE CONDITIONED FLOOR
 AREA, HOT WATER SYSTEM, AND HVAC
 CREDITS. SAME ENERGY CAL'S. WERE
 RESUBMITTED.
  
 2) AS NOTED IN LAST REVIEW 6-5-06 #6.
 ALL RETURN AIR TRANSFER DUCTS ARE TO
 SMALL. RETURN AIR TRANSFER DUCTS NEED TO
 BE 1 1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCTS
 ENTERING THE ROOM. THE MASTER SUITE MUST
 INCLUDE THE BATHROOM AND CLOSET. PER
 2004 FBC/R M1602.4 .
  
 3) CLOTHES DRYER VENTS CAN NOT HAVE
 SCREENS IN THEM, PER 2004 FBC/R M1501.1,
 PLEASE CORRECT.
  
 4) THE CLOTHES DRYER VENT AND THE GAS
 WATER HEATER VENT CAN NOT DISCHARGE TO
 THE COVERED PORCH, PER 2004 FBC/M 501.2,
 PLEASE CORRECT.
  
 5) SEE PAGE SP-1, D-1, A-1, S-2 ARE
 SHOWING EXISTING CU-1 CONDENSER UNIT TO
 REMAIN, WERE PAGE E-1 SHOWS EXIST. CU-1
 TO BE REPLACED, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.