| Plan Review Notes For Permit 06050213 |
| Permit Number |
06050213 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-12 00:00:00 | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 6-5-06 #2. | | | PLEASE MAKE CORRECTIONS TO ENERGY | | | CALCULATIONS, SEE CONDITIONED FLOOR | | | AREA, HOT WATER SYSTEM, AND HVAC | | | CREDITS. SAME ENERGY CAL'S. WERE | | | RESUBMITTED. | | | | | | 2) AS NOTED IN LAST REVIEW 6-5-06 #6. | | | ALL RETURN AIR TRANSFER DUCTS ARE TO | | | SMALL. RETURN AIR TRANSFER DUCTS NEED TO | | | BE 1 1/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCTS | | | ENTERING THE ROOM. THE MASTER SUITE MUST | | | INCLUDE THE BATHROOM AND CLOSET. PER | | | 2004 FBC/R M1602.4 . | | | | | | 3) CLOTHES DRYER VENTS CAN NOT HAVE | | | SCREENS IN THEM, PER 2004 FBC/R M1501.1, | | | PLEASE CORRECT. | | | | | | 4) THE CLOTHES DRYER VENT AND THE GAS | | | WATER HEATER VENT CAN NOT DISCHARGE TO | | | THE COVERED PORCH, PER 2004 FBC/M 501.2, | | | PLEASE CORRECT. | | | | | | 5) SEE PAGE SP-1, D-1, A-1, S-2 ARE | | | SHOWING EXISTING CU-1 CONDENSER UNIT TO | | | REMAIN, WERE PAGE E-1 SHOWS EXIST. CU-1 | | | TO BE REPLACED, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|