| Plan Review Notes For Permit 06050213 |
| Permit Number |
06050213 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-11 00:00:00 | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ENGINEERING FIRM SHALL INDICATE | | | THE CERTIFICATE OF AUTHORIZATIONNUMBER | | | ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 | | | FLORIDA ADMINISTRATIVE | | | CODE. | | | | | | 2} SHEET SP-1 INDICATES THE EXISTING A/C | | | UNIT TO REMAIN AND ADDING A/C-2. THERE | | | IS ONLY ONE SYSTEM ON THE ELECTRICAL | | | PLAN, PLEASE CLARIFY, CORRECT THE PANEL | | | SCHEDULE AND LOAD CALCS IF NECESSARY. | | | | | | 3} THE DRYER CIRCUIT INDICATES A #12 | | | CONDUCTOR ON THE 25 AMP BREAKER. THE | | | CONDUCTOR MUST BE #10 TO COMPLY WITH | | | 240.4(D). | | | | | | 4} RESEPTACLES MUST BE ADDED IN THE | | | DINING AND MASTER BED ROOMS PER 210.52. | | | | | | 5} PLEASE PROVIDE A PANEL SCHEDULE SO | | | THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND | | | OVER CURRENT PROTECTION COMPLIANCE MAY | | | BE REVIEWED. | | | NOTE: A LOAD CALCULATION AND PANEL | | | SCHEDULE ARE REQUIRED PER 106.3.5.4, FBC | | | AS AMENDED. | | | | | | 6} TWO COMPLETE SETS OF DOCUMENTS ARE | | | REQUIRED TO BE SUBMITTED FOR REVIEW PER | | | 106.1 FBC, AS AMENDED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|