Plan Review Notes
Plan Review Notes For Permit 06050213
Permit Number 06050213
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-11 00:00:00 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEERING FIRM SHALL INDICATE
 THE CERTIFICATE OF AUTHORIZATIONNUMBER
 ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE
 CODE.
  
 2} SHEET SP-1 INDICATES THE EXISTING A/C
 UNIT TO REMAIN AND ADDING A/C-2. THERE
 IS ONLY ONE SYSTEM ON THE ELECTRICAL
 PLAN, PLEASE CLARIFY, CORRECT THE PANEL
 SCHEDULE AND LOAD CALCS IF NECESSARY.
  
 3} THE DRYER CIRCUIT INDICATES A #12
 CONDUCTOR ON THE 25 AMP BREAKER. THE
 CONDUCTOR MUST BE #10 TO COMPLY WITH
 240.4(D).
  
 4} RESEPTACLES MUST BE ADDED IN THE
 DINING AND MASTER BED ROOMS PER 210.52.
  
 5} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH/FEEDER CIRCUIT CONDUCTOR AND
 OVER CURRENT PROTECTION COMPLIANCE MAY
 BE REVIEWED.
 NOTE: A LOAD CALCULATION AND PANEL
 SCHEDULE ARE REQUIRED PER 106.3.5.4, FBC
 AS AMENDED.
  
 6} TWO COMPLETE SETS OF DOCUMENTS ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW PER
 106.1 FBC, AS AMENDED.
  