Plan Review Notes
Plan Review Notes For Permit 06050213
Permit Number 06050213
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-05 00:00:00DENIED;
 SANITARY RISER DIAGRAM;
 AUTOMATIC CLOTHES WASHER IS REQUIRED
 DISCHARGE INDIRECTLY INTO A STANDPIPE A
 MINIMUM OF 18" NOT INTO A FLOOR DRAIN,
 SEE FBC-2004 PLUMBING SEC.802.4.
 2.W/M AND KITCHEN SINK SHALL NOT DRAIN
 INTO THE WET VENT OF A BATHROOM GROUP.
 SEC. 909.1.
 3.BRANCH DRAIN FOR W/M SHALL BE 3", SEC.
 406.3
 WATER RISER DIAGRAM;
 1.WATER HAMMER ARRESTORS ARE REQUIRED
 PER SEC. 604.9
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695