| Date |
Text |
| 2006-06-05 00:00:00 | *** DENIED *** |
| | 1) ENGINEER'S PRINTED NAME MUST APPEAR |
| | IN THE TITLE BLOCK, ALSO THE ENGINEERING BUSINESS'S |
| | CERTIFICATE OF AUTHORIZATION |
| | NUMBER, PER FAC 61G15-23.002 . |
| | |
| | 2) PLEASE MAKE CORRECTIONS TO ENERGY |
| | CALCULATIONS, SEE CONDITIONED FLOOR |
| | AREA, HOT WATER SYSTEM, AND HVAC |
| | CREDITS. |
| | |
| | 3) PROVIED COMBUSTION AIR FOR GAS WATER |
| | HEATER AND GAS CLOTHES DRYER, PER 2004 |
| | FBC/R M1701.1 . |
| | |
| | 4) PLEASE SUBMIT A MANUAL 'D' |
| | CALCULATION (RESIDENTIAL DUCT DESIGN), |
| | PER 2004 FBC/R M1601.1 . |
| | |
| | 5) RETURN AIR GRILL 20" X 20" WITH A |
| | FILTER IS TO SMALL FOR A 4 TON SYSTEM, |
| | PLEASE CORRECT. |
| | |
| | 6) ALL THE RETURN AIR TRANSFER GRILLS |
| | ARE TO SMALL, SEE NOTE #7. |
| | |
| | 7) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |