Plan Review Notes
Plan Review Notes For Permit 06050208
Permit Number 06050208
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-10 00:00:00********* UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME NOTE FROM THE
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED. PLEASE SEE COMMENT BELOW ARE
 TAKEN DIRECTLY FROM THE PREVIOUS REVIEW.
 PLEASE KNOW SOME INFORMATION(SPECS) ARE
 ONLY NOW BEING REVIEWED FOR THE FIRST
 TIME.
  
 ** PLEASE KNOW PERMIT APPLICATION WAS
 ONCE AGAIN SUBMITTED WITH THE ADDRESS OF
 "4826" N. HAVERHILL WHICH IS THE ADDRESS
 FOR "COTTAGE #10". PLEASE SEE PLANS NOW
 INDICATE "4884" N. HAVERHILL WHICH IS
 THE ADDRESS FOR WHAT WAS/IS GOING TO BE
 THE ADMIN BLDG.
 **PLEASE SEE THE ADDRESS FOR THIS
 PROJECT IS LOCATED AT THE SOCIAL
 BUILDING WHICH IS "4888" N HAVERHILL RD.
  
 THIS REVIEWER HASPERSONALLY CHANGED
 OUR SYSTEM, MOVED PERMITS TO THE "4884"
 AND HAS CHANGED THE PERMIT APPLICATION
 TO READ 4888.
 PLEASE SEE PLANS/TITLE BLOCKS ARE
 SHOWING 4884, WHICH WAS GOING TO BE
 CHANGED BY HAND HOWEVER PLANS ARE COMING
 BACK FOR CORRECTIONS, PLEASE REVISE AT
 THAT TIME.
  
 1) NOTE: NO, PLEASE SEE THE SAME SHEET
 WAS SUBMITTED BACK FOR SLAB DETAIL, IN
 FACT A "COLORED PHOTO-COPY" WAS MADE OF
 THE SAME SHEETS WHICH THIS REVIEWER
 HIGHLIGHTED AND REDLINED "COPY" . PLEASE
 KNOW THIS IS 2ND TIME THIS NOTE IS
 STATED THAT ALL PLANS, DETAILS ETC DONE
 BY AN ENGINEER SHALL CONTAIN AN ORIGINAL
 SIGNATURE, DATE AND SEAL.
 PLEASE KNOW THAT A "RAISED SEAL" OVER A
 DOCUMENT WHICH IS A PHOTO-COPY OF THE
 ENGINEER'S SIGNATURE IS NOT ACCEPTABLE.
 IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE CONTACT MR. PAUL MARTIN EXECUTIVE
 DIRECTOR FOR THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEER'S AND MR. JERRY
 ONGLEY INVESTIGATOR TO THE BOARD. THEY
 HAVE BEEN CONTACTED ON THIS MATTER AND
 PENDING BUILDING OFFICIAL'S RULING,
 PLANS WHICH WERE RETAINED ON THE
 PREVIOUS REVIEW AND PLANS NOW BEING
 RETAINED ON THIS REVIEW MAY BE FORWARDED
 TO THE STATE FBPE'S FOR REVIEW.
 PLEASE SEE FAC 61G15-23.002, AND FS
 471.025. PLEASE STILL MISSING LICENSE
 NUMBER WHICH WAS NOT AS THE SAME
 SHEET(S) WERE SUBMITTED BACK FOR REVIEW.
 IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE ALSO DO NOT HESITATE IN
 CONTACTING THIS REVIEWER (# BELOW ) OR
 THEDIRECTOR/BUILDING OFFICIALMR.
 NEIL MELICK @ 561-805-6654
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE BE SURE ALL SHEETS
 CONTAIN AN ORIGINAL SIGNATURE. PLEASE
 SEE SLAB DETAIL SHEET CONTAINS A RAISED
 SEALED OVER A PHOTO-COPIED SIGNATURE FOR
 THE ENGINEER OF RECORD.
 PLEASE KNOW, ONE COPY IS BEING RETAINED
 FOR FILE.
 FS 471.025,FAC 61G15-23.002
  
 2) NOTE: NO, THIS WAS ADJUSTED BY THE
 OFFICE BASED ON THE MARSHALL'S /SWIFT
 GUIDE WHICH IS ADOPTED BY THE FBC AND
 FEES OF $488.80 ARE NOW DUE BEFORE
 PERMIT CAN BE ISSUED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS, EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED. PLEASE SEE VALUE AT
 30,000 IS WAY LOW FOR SCOPE.
 108.3 FBC
  
 3) NOTE: OK, SPEC ARE NOW SUBMITTED.
 THIS IS THE FIRST TIME THIS OFFICE HAS
 REVIEWED SPECS.
 ** PLEASE SEE SPECS ARE SHOWING A 3-POLE
 ATS WHICH DOES NOT CORRELATE WITH THE
 PLANS. PLEASE SEE COMMENT BELOW WITH
 RESPECT TO THE "SEPARATELY DERIVED
 SYSTEM".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPECS FOR
 GENERATOR AND ATS. SPECS FOR GEN WERE
 SUBMITTED HOWEVER COULD NOT LOCATE THE
 LISTING FROM A NRTL.
 PLEASE ALSO SEE NO SPECS FOR THE ATS
 WERE SUBMITTED.
  
 4) NOTE:NO, PLEASE SEE THE GENERATOR
 ON PLANS ARE NOW SHOWING A 4-POLE ATS
 AND CONDUCTORS FROM THE GEN TO THE
 BUILDING IS INDICATING A SD SYSTEM,
 HOWEVER PLEASE INCLUDE A NEW GROUNDING
 ELECTRODE SYSTEM AT GENERATOR AS
 REQUIRED PER 250.50,250.20.
 THIS IS ONE ITEM THAT SHOULD REALLY BE
 DISCUSSED AND COORDINATED WITH OWNER'S,
 CONTRACTOR AND DESIGN TEAM ON WHICH
 SYSTEM IS GOING TO BE INSTALLED AS SPECS
 SHEETS FOR EQUIPMENT ORDERED FROM
 MANUFACTURE DOES NOT CORRELATE.
 IF THERE ARE QUESTIONS ON THIS AND THIS
 OFFICE CAN BE OF ASSISTANCE, PLEASE DO
 NOT HESITATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CONDUCTORS SHOWN
 FROM GENERATOR TO THE ATS TEND TO LEND
 GENERATOR BEING A SEPARATELY DERIVED
 SYSTEM, YET THE ATS IS SHOWN AS 3-POLE?
 PLEASE CLARIFY AND SHOW GROUNDING PER
 250.30.
 IF NOT A SDS, THEN PLEASE INCLUDE THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122 ETC
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 ** NEW NOTE **
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS. THIS IS ONLY
 A NOTICE GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  