| Plan Review Notes For Permit 06050208 |
| Permit Number |
06050208 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-19 00:00:00 | 1. PLANS THAT WERE SUBMITTED WERE TWO | | | SHEETS OF E5-4.01. THESE SHEETS DO NOT | | | INDICATE WHERE THE DIESEL GENERATOR WILL | | | BE INSTALLED WITH RESPECT TO BUILDINGS, | | | DOORS, WINDOWS, ETC. | | | | | | 2. THE BASE TANK MEETS WHICH RECOGNIZED | | | CRITERIA TO CONTAIN DIESEL FUEL. IS IT | | | DESIGNED TO SUPPORT THE WEIGHT OF THE | | | GENERATOR. | | | | | | 3. WHAT IS THE PROPOSED GENERATOR GOING | | | TO SUPPLY. EMERGENCY EQUIPMENT OR | | | CONVENIENCE EQUIPMENT. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|