Plan Review Notes
Plan Review Notes For Permit 06050208
Permit Number 06050208
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-02 00:00:00************* UNSAT ***************
  
 1) NOTE: PLEASE BE SURE ALL SHEET
 CONTAIN AN ORIGINAL SIGNATURE. PLEASE
 SEE SLAB DETAIL SHEET CONTAINS A RAISED
 SEALED OVER A PHOTO-COPIED SIGNATURE FOR
 THE ENGINEER OF RECORD.
 PLEASE KNOW, ONE COPY IS BEING RETAINED
 FOR FILE.
 FS 471.025,FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS, EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED. PLEASE SEE VALUE AT
 30,000 IS WAY LOW FOR SCOPE.
 108.3 FBC
  
 3) NOTE: PLEASE SUBMIT THE SPECS FOR
 GENERATOR AND ATS. SPECS FOR GEN WERE
 SUBMITTED HOWEVER COULD NOT LOCATE THE
 LISITNG FROM A NRTL.
 PLEASE ALSO SEE NO SPECS FOR THE ATS
 WERE SUBMITTED.
  
 4) NOTE: PLEASE SEE CONDUCTORS SHOWN
 FROM GENERATOR TO THE ATS TEND TO LEND
 GENERATOR BEING A SEPARATELY DERIVED
 SYSTEM, YET THE ATS IS SHOWN AS 3-POLE?
 PLEASE CLARIFY AND SHOW GROUNDING PER
 250.30.
 IF NOT A SDS, THEN PLEASE INCLUDE THE
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122 ETC
  
 5) NOTE: PLEASE SEE A DISCONNECTING
 MEANS FOR FEEDERS COMING FROM THE
 GENERATOR IS REQUIRED AND IS TO BE
 GROUPED WITH THE SERVICE MEANS OF
 DISCONNECT PER 225.31-225.39.
  
 6) NOTE: PLEASE PROVIDE A SITE OVERVIEW
 SHOWING THE LOCATIONS OF ALL EQUIPMENT,
 DISC'S AND GEN.
 215.3
  
 7) NOTE: PLEASE BE SURE AIC RATINGS ARE
 INDICATED FOR THE ATS AND ANY NEW
 DISCONNECTS.
 110.9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]