| 2006-06-02 00:00:00 | ************* UNSAT *************** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL SHEET |
| | CONTAIN AN ORIGINAL SIGNATURE. PLEASE |
| | SEE SLAB DETAIL SHEET CONTAINS A RAISED |
| | SEALED OVER A PHOTO-COPIED SIGNATURE FOR |
| | THE ENGINEER OF RECORD. |
| | PLEASE KNOW, ONE COPY IS BEING RETAINED |
| | FOR FILE. |
| | FS 471.025,FAC 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE VALUE FOR SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR AND |
| | MATERIALS, EVEN IF ANY EQUIPMENT IS |
| | OWNER SUPPLIED. PLEASE SEE VALUE AT |
| | 30,000 IS WAY LOW FOR SCOPE. |
| | 108.3 FBC |
| | |
| | 3) NOTE: PLEASE SUBMIT THE SPECS FOR |
| | GENERATOR AND ATS. SPECS FOR GEN WERE |
| | SUBMITTED HOWEVER COULD NOT LOCATE THE |
| | LISITNG FROM A NRTL. |
| | PLEASE ALSO SEE NO SPECS FOR THE ATS |
| | WERE SUBMITTED. |
| | |
| | 4) NOTE: PLEASE SEE CONDUCTORS SHOWN |
| | FROM GENERATOR TO THE ATS TEND TO LEND |
| | GENERATOR BEING A SEPARATELY DERIVED |
| | SYSTEM, YET THE ATS IS SHOWN AS 3-POLE? |
| | PLEASE CLARIFY AND SHOW GROUNDING PER |
| | 250.30. |
| | IF NOT A SDS, THEN PLEASE INCLUDE THE |
| | EQUIPMENT GROUNDING CONDUCTOR. |
| | 250.110,250.122 ETC |
| | |
| | 5) NOTE: PLEASE SEE A DISCONNECTING |
| | MEANS FOR FEEDERS COMING FROM THE |
| | GENERATOR IS REQUIRED AND IS TO BE |
| | GROUPED WITH THE SERVICE MEANS OF |
| | DISCONNECT PER 225.31-225.39. |
| | |
| | 6) NOTE: PLEASE PROVIDE A SITE OVERVIEW |
| | SHOWING THE LOCATIONS OF ALL EQUIPMENT, |
| | DISC'S AND GEN. |
| | 215.3 |
| | |
| | 7) NOTE: PLEASE BE SURE AIC RATINGS ARE |
| | INDICATED FOR THE ATS AND ANY NEW |
| | DISCONNECTS. |
| | 110.9 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |