| Plan Review Notes For Permit 06050195 |
| Permit Number |
06050195 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-06-11 09:46:21 | DENIED; | | | 1. DRINKING FOUNTAIN NOT SHOWN ON SANITARY RISER | | | DIAGRAM OR ON PAGE # 6, FLAT PLUMBING DRAWING. | | | 2. DRINKING FOUNTAIN MUST BE RECESSED. ( SHOW ON | | | DRAWING NOT 8 X 11 PAGE). | | | 3. CHANGE NOTES ON PAGE 10 " DEMO PLAN" ,FOR BATHROOM | | | FIXTURESTO BE REMOVED, TO READ "NO DEAD ENDS PERMITED | | | IN THE PLUMBING SYSTEM. REMOVE ALL PIPES BACK TO THE | | | BUILDING DRAIN AND HARD CAP". FBC-2004 PLUMBING SECTION | | | 704.5. | | | 4. ADD NOTE TO DEMO PAGE 10"PLUMBING DEMO TO BE DONE | | | BY A LICENSED PLUMBING CONTRACTOR, PERMIT AND | | | INSPECTIONS REQUIRED". | | | 5.ADD NOTE TO PAGE # 2, " IF SPACES 5 AND 6 DO NOT HAVE | | | ACCESS TO HALL WAY A DRINKING FOUNTAIN SHALL BE | | | INSTALLED PER FBC-2004 PLUMBING TABLE 403.1". | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|