Plan Review Notes
Plan Review Notes For Permit 06050195
Permit Number 06050195
Review Stop P
Sequence Number 6
Notes
Date Text
2007-06-11 09:46:21DENIED;
 1. DRINKING FOUNTAIN NOT SHOWN ON SANITARY RISER
 DIAGRAM OR ON PAGE # 6, FLAT PLUMBING DRAWING.
 2. DRINKING FOUNTAIN MUST BE RECESSED. ( SHOW ON
 DRAWING NOT 8 X 11 PAGE).
 3. CHANGE NOTES ON PAGE 10 " DEMO PLAN" ,FOR BATHROOM
 FIXTURESTO BE REMOVED, TO READ "NO DEAD ENDS PERMITED
 IN THE PLUMBING SYSTEM. REMOVE ALL PIPES BACK TO THE
 BUILDING DRAIN AND HARD CAP". FBC-2004 PLUMBING SECTION
 704.5.
 4. ADD NOTE TO DEMO PAGE 10"PLUMBING DEMO TO BE DONE
 BY A LICENSED PLUMBING CONTRACTOR, PERMIT AND
 INSPECTIONS REQUIRED".
 5.ADD NOTE TO PAGE # 2, " IF SPACES 5 AND 6 DO NOT HAVE
 ACCESS TO HALL WAY A DRINKING FOUNTAIN SHALL BE
 INSTALLED PER FBC-2004 PLUMBING TABLE 403.1".
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695