2007-04-13 14:22:09DENIED;
 I AM SENDING A COPY OF MY LAST 4 PLUMBING PLAN REVIEWS
 THE THIS 5TH PLUMBING PLAN REVIEW, TO SHOW THE SAME
 COMMENTS HAVE NOT BEEN ADDRESSED. I HAVE ALSO MARKED
 ONE SET OF PLANS IN RED AND YELLOW HIGHLIGHTER FOR YOUR
 REVIEW.
 1. PER OUR PHONE CONVERSATION ABOUT DRINKING FOUNTAINS,
 I AGREED THAT ONE DRINKING FOUNTAIN COULD BE INSTALLED
 IF ALL BAYS HAD ACCESS. BAY 5 AND 6 DO NOT HAVE ACCESS
 TO THE HALL WAY. DRINKING FOUNTAIN WOULD BE REQUIRED IN
 THOSE 2 BAYS. ON PAGE 2 YOU SHOW A BOTTLE WATER
 DISPENSOR AND ON PAGE 8A DIAGRAM OF A BOTTLE WATER
 COOLER IS SHOWN. A DRINKING FOUNTAIN IS REQUIRED AND
 CANNOT BE SUBSTITUTED WITH BOTTLE WATER. SEE FBC-2004
 PLUMBING SECTION 410.1. THE DRINKING FOUNTAINS MUST
 MEET HANDICAP REQUIREMENTS IN CHAPER 11 OF THE BUILDING
 CODE SECTIONS 11-4.1.3(10) AND SECTIONS 11-4.15.1 THRU
 11-4.15. 5. SHOW CUP HOLDER FOR PEOPLE FOR PEOPLE WITH
 BAD BACKS. IF A DRINKING FOUNTAIN IS IN A HALE WAY IT
 MUST BE RECESSED SO IT WILL NOT BE AN OBSTRUCTION THAT
 BE BE BUMPED INTO. SEE FIGURE 27(D), A COPY IS GLUED
 ONTO PAGE 8 ALSO.
 2. WATER CLOSET IN BAY 7 IS STILL NOT VENTED. THE
 BRANCH DRAINFROM THE W/C GOES TO THE BUILDING DRAIN
 WITHOUT A VENT. THERE ARE TOO MANY FIXTURE UNITS ON THE
 BUILDING DRAIN TO WET VENT W/C #7. SEE TABLE 909.3 WET
 VENT SIZING.
 3. BUILDING DRAIN SIZE IS NOT CORRECT. SEE
 TABLE710.1(1) THREE INCH. PIPE AT 1/4" PITCH CAN CARRYA
 MAXUMUM OF 42 FU'S PLANS SHOW A TOTAL OF 64FU'S. PIPE
 SIZE MUST INCRESS TO 4" AFTER BATHROON # 4.
 4. WATER RISER DIAGRAM PAGE 6.1. EXTEND 1" WATER PIPE
 TO BATHROOM 3.
 PLEASE READ THE IMPORTANT NOTICE THAT IS
 ATTACHED TO MY PLUMBING PLAN REVIEWS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695