| 2007-04-13 14:22:09 | DENIED; |
| | I AM SENDING A COPY OF MY LAST 4 PLUMBING PLAN REVIEWS |
| | THE THIS 5TH PLUMBING PLAN REVIEW, TO SHOW THE SAME |
| | COMMENTS HAVE NOT BEEN ADDRESSED. I HAVE ALSO MARKED |
| | ONE SET OF PLANS IN RED AND YELLOW HIGHLIGHTER FOR YOUR |
| | REVIEW. |
| | 1. PER OUR PHONE CONVERSATION ABOUT DRINKING FOUNTAINS, |
| | I AGREED THAT ONE DRINKING FOUNTAIN COULD BE INSTALLED |
| | IF ALL BAYS HAD ACCESS. BAY 5 AND 6 DO NOT HAVE ACCESS |
| | TO THE HALL WAY. DRINKING FOUNTAIN WOULD BE REQUIRED IN |
| | THOSE 2 BAYS. ON PAGE 2 YOU SHOW A BOTTLE WATER |
| | DISPENSOR AND ON PAGE 8A DIAGRAM OF A BOTTLE WATER |
| | COOLER IS SHOWN. A DRINKING FOUNTAIN IS REQUIRED AND |
| | CANNOT BE SUBSTITUTED WITH BOTTLE WATER. SEE FBC-2004 |
| | PLUMBING SECTION 410.1. THE DRINKING FOUNTAINS MUST |
| | MEET HANDICAP REQUIREMENTS IN CHAPER 11 OF THE BUILDING |
| | CODE SECTIONS 11-4.1.3(10) AND SECTIONS 11-4.15.1 THRU |
| | 11-4.15. 5. SHOW CUP HOLDER FOR PEOPLE FOR PEOPLE WITH |
| | BAD BACKS. IF A DRINKING FOUNTAIN IS IN A HALE WAY IT |
| | MUST BE RECESSED SO IT WILL NOT BE AN OBSTRUCTION THAT |
| | BE BE BUMPED INTO. SEE FIGURE 27(D), A COPY IS GLUED |
| | ONTO PAGE 8 ALSO. |
| | 2. WATER CLOSET IN BAY 7 IS STILL NOT VENTED. THE |
| | BRANCH DRAINFROM THE W/C GOES TO THE BUILDING DRAIN |
| | WITHOUT A VENT. THERE ARE TOO MANY FIXTURE UNITS ON THE |
| | BUILDING DRAIN TO WET VENT W/C #7. SEE TABLE 909.3 WET |
| | VENT SIZING. |
| | 3. BUILDING DRAIN SIZE IS NOT CORRECT. SEE |
| | TABLE710.1(1) THREE INCH. PIPE AT 1/4" PITCH CAN CARRYA |
| | MAXUMUM OF 42 FU'S PLANS SHOW A TOTAL OF 64FU'S. PIPE |
| | SIZE MUST INCRESS TO 4" AFTER BATHROON # 4. |
| | 4. WATER RISER DIAGRAM PAGE 6.1. EXTEND 1" WATER PIPE |
| | TO BATHROOM 3. |
| | PLEASE READ THE IMPORTANT NOTICE THAT IS |
| | ATTACHED TO MY PLUMBING PLAN REVIEWS. |