| Notes |
| Date |
Text |
| 2007-03-03 09:47:09 | DENIED; | | | FOURTH PLUMBING REVIEW. COMMENTS FROM REVIEW # 3 WERE | | | NOT ADDRESSED. SHOW DATE OF REVISION ON PLANS AND CLOUD | | | CHANGES FOR CLARITY. | | | 1. DRINKING FOUNTAINS ARE REQUIRED IN EACH UNIT. SEE | | | FBC-2004 PLUMBING TABLE 403.1(6M). AND SECTION 410.1. | | | 2. SANITARY RISER DIAGRAM; | | | A) TOILET IN BAY 7 IS NOT VENTED. ( ONE SET OF | | | PLANS MARKED IN RED) | | | B) TABLE 710.1(1) ONLY 42 FIXTURES PERMITED ON 3" | | | AT 1/4" PER FT PITCH. | | | 3. WATER PIPE SIZING NOT CORRECT. SEE TABLE 603.1 ( SEE | | | ONE SET OF PLANS MARKED IN RED) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|