2007-03-03 09:47:09DENIED;
 FOURTH PLUMBING REVIEW. COMMENTS FROM REVIEW # 3 WERE
 NOT ADDRESSED. SHOW DATE OF REVISION ON PLANS AND CLOUD
 CHANGES FOR CLARITY.
 1. DRINKING FOUNTAINS ARE REQUIRED IN EACH UNIT. SEE
 FBC-2004 PLUMBING TABLE 403.1(6M). AND SECTION 410.1.
 2. SANITARY RISER DIAGRAM;
 A) TOILET IN BAY 7 IS NOT VENTED. ( ONE SET OF
 PLANS MARKED IN RED)
 B) TABLE 710.1(1) ONLY 42 FIXTURES PERMITED ON 3"
 AT 1/4" PER FT PITCH.
 3. WATER PIPE SIZING NOT CORRECT. SEE TABLE 603.1 ( SEE
 ONE SET OF PLANS MARKED IN RED)
 PLUMBING PLAN REVIEW BY;