| Plan Review Notes For Permit 06050195 |
| Permit Number |
06050195 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-01-08 09:09:34 | DENIED; | | | 1.DRINKING FOUNTAINS REQUIRED FBC-2004 PLUMBING CODE | | | TABLE 403.1 (6M). | | | 2.SANITARY RISER DIAGRAM; | | | (A)W/C IN BAY 7 IS NOT VENTED. | | | (B)PIPE SIZE NOT CORRECT SEE TABLE710.1. | | | 3. WATER PIPE SIZING TO SMALL, SEE APPENDIX E OF THE | | | PLUMBING CODE, | | | TABLE E103.3(2) LOAD VALUES | | | TABLE E103.3(3) ESTIMATING DEMAND | | | FIGURE E103.3(3). | | | NOTE; FLUID VALOCITIES IN EXCESS OF 5 TO 8 FT/SEC | | | ARE NOT RECOMMENDED. VALOCITY OF SERVICE PIPE WOULD BE | | | OVER 10 FT/SEC. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|