2007-01-08 09:09:34DENIED;
 1.DRINKING FOUNTAINS REQUIRED FBC-2004 PLUMBING CODE
 TABLE 403.1 (6M).
 2.SANITARY RISER DIAGRAM;
 (A)W/C IN BAY 7 IS NOT VENTED.
 (B)PIPE SIZE NOT CORRECT SEE TABLE710.1.
 3. WATER PIPE SIZING TO SMALL, SEE APPENDIX E OF THE
 PLUMBING CODE,
 TABLE E103.3(2) LOAD VALUES
 TABLE E103.3(3) ESTIMATING DEMAND
 FIGURE E103.3(3).
 NOTE; FLUID VALOCITIES IN EXCESS OF 5 TO 8 FT/SEC
 ARE NOT RECOMMENDED. VALOCITY OF SERVICE PIPE WOULD BE
 OVER 10 FT/SEC.