| 2006-12-20 17:38:22 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | PREVIOUS COMMENTS NOT CORRECTLY ADDRESSED, PRIOR NUMBER |
| | USED. |
| | |
| | 2} SEE ARTICLE 440-22 AND VERIFY THE OCP |
| | FOR THE ACU MEETS THESE PERAMETERS. ALL |
| | PANELS. SEE HOUSE PANEL. 60 AMP, 2 POLE, WITH #10 |
| | CONDUCTORS. |
| | |
| | 3} THERE IS NO PARKING LOT LIGHTING |
| | BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN |
| | THE HOUSE PANEL. PLEASE VERIFY AND |
| | INDICATE HOW LIT. |
| | |
| | 4} THE CIRCUITING FOR THE EMERGENCY WALL |
| | LIGHTS MUST BE CIRCUITED WITH THE MAIN |
| | LIGHTING IN THE AREA, SEE 700.12(5)(E). THERE IS A NOTE |
| | REFERENCING COMPLIANCE,. BUT THE CIRCUIT NUMBERS ON THE |
| | PLAN ARE NOT CORRECT. SEE SHEET 3. |
| | |
| | 5} PLEASE SUBMIT THE CORRECT ENERGY |
| | CALCULATION FORM AND INDICATE COMPLIANCE |
| | 13-414 AND 415 ON THE PLANS. SHOW |
| | OCCUPANCY SENSORS, TIMERS, ETC. |
| | |
| | NEW COMMENTS, THIS REVIEW. |
| | |
| | 6} ELECTRICAL NOTES #4 & 7 REFERENCED ARTICLES ARE NOT |
| | IN THE 2004 FBC. PLEASE CLARIFY. |
| | |
| | 7} THE ARCHITECTS SEAL IS NOT DISCERNIBLE. SEE 61G1-16 |
| | FAC. PLEASE RESEAL ALL SHEETS. |
| | |
| | THE FIRST 4 COMMENTS WERE ON THE |
| | PREVIOUS REVIEW. PLEASE PROVIDE WRITTEN RESPONSE |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |