Plan Review Notes
Plan Review Notes For Permit 06050195
Permit Number 06050195
Review Stop E
Sequence Number 3
Notes
Date Text
2006-12-20 17:38:22 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PREVIOUS COMMENTS NOT CORRECTLY ADDRESSED, PRIOR NUMBER
 USED.
  
 2} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS. SEE HOUSE PANEL. 60 AMP, 2 POLE, WITH #10
 CONDUCTORS.
  
 3} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 4} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E). THERE IS A NOTE
 REFERENCING COMPLIANCE,. BUT THE CIRCUIT NUMBERS ON THE
 PLAN ARE NOT CORRECT. SEE SHEET 3.
  
 5} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS. SHOW
 OCCUPANCY SENSORS, TIMERS, ETC.
  
 NEW COMMENTS, THIS REVIEW.
  
 6} ELECTRICAL NOTES #4 & 7 REFERENCED ARTICLES ARE NOT
 IN THE 2004 FBC. PLEASE CLARIFY.
  
 7} THE ARCHITECTS SEAL IS NOT DISCERNIBLE. SEE 61G1-16
 FAC. PLEASE RESEAL ALL SHEETS.
  
 THE FIRST 4 COMMENTS WERE ON THE
 PREVIOUS REVIEW. PLEASE PROVIDE WRITTEN RESPONSE
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026