2007-01-05 10:25:21BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
  
 1 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)WHAT TOILET IS USED BY 'STO 1' AND 'STO 2'.
 INDICATE WHICH BATHROOM WILL BE USED BY THESE SPACES.
  
 3)ON PAGE #1THE NOTE WHICH REFEERS TO CH. 34 SHALL
 EITHER BE REMOVED OR STRIKE OUT BECAUSE THE SECTIONS IT
 REFERENCES ARE IN THE 2001 FBC.
  
 4)THE ARCHITECT'S SEAL SHALL BE LEGIBLE ON EACH
 SHEET. THE SEAL IS NOT CLEAR ON SOME SHEETS. SEE 61G-16
 FAC.
  
 5)FBC.106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL COMFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5).A WALL LEGEND IS REQUIRED TO SHOW WHICH
 WALLS WILL BE DEMO AND THE NEW TYPES OF WALLS. SHOW THE
 THIS INFORMATION SHALL BE CLEARLY INDICATED ON THE
 DRAWINGS.
  
 6)SHOW IN DETAIL HOW THE NEW FACIA WILL BE ATTATCHED
 TO THE BUILDING.
  
 7)708.3 FIRE -RESISTANCE RATING.
 THE FIRE -RESISTANCE RATING OF THE WALLS SHALL BE AT
 LEAST 1 HOUR FOR INDIVIDUAL TENANT SPACES. (SEE
 FBC.708.1 AND 708.4)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  