| Plan Review Notes For Permit 06050195 |
| Permit Number |
06050195 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-09 00:00:00 | DENIED; | | | 1.(SECOND REQUEST) TYPE OF OCCUPANCY NOT | | | SHOWN. SEE FBC-2004 EXISTING BUILDING | | | CODE SECTION 810.1. IF CHANGE OF | | | OCCPANCY THEN DRINKING FOUNTAINS ARE | | | REQUIRED. BOTTLE WATER CAN NOT BE USED | | | AS A SUBSTITUTE SEE PLUMBING CODE | | | SECTION 410.1. | | | 2.(SECOND REQUEST) WATER AND SANITARY | | | RISER DIAGRAMS ARE REQUIRED. SEE CHAPTER | | | 1 WPB AMENDMENTS, SECTION | | | 106.3.5.1.3(13). | | | 3.(SECOND REQUEST) BACLFLOW PROTECTION | | | REQUIRED ON WATER SERVICE. SHOW ON PLAN | | | OR ADD NOTE TO PLAN. | | | 4.(SECOND REQUEST) SHOW MINIMUM SLOPE | | | ON HORIZONTAL 3" DRAIN PIPE WITH 40 FU"S | | | IS 1/4" PER FOOT. NOT SHOWN ON PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|