| Plan Review Notes For Permit 06050195 |
| Permit Number |
06050195 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-13 00:00:00 | ***DENIED*** | | | | | | SOME REVISIONS TO PLANS ARE NOTED | | | HOWEVER SOME COMMENTS FROM PREVIOUS | | | REVIEW NEED TO BE ACKNOWLEDGED. | | | | | | 1) PLEASE DEFINE OCCUPANCY TYPE IN | | | ACCORDANCE WITH FBC AND NFPA 101, | | | CHAPTER 6 FOR ALL SPACES SHOWN ON PLANS. | | | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. PLEASE ADD TO PLANS. | | | | | | 3) OK- REMOVED FROM PLANS. | | | | | | 4) OK- REMOVED FROM PLANS. | | | | | | 5) OK | | | | | | 6) STROBES APPEAR TO HAVE BEEN REMOVED | | | FROM INDIVIDUAL SPACES, BUT STILL ARE | | | SHOWING IN CORRIDOR. AGAIN, PLEASE | | | ADVISE WHAT STROBES ARE CONNECTED TO. IS | | | THERE AN EXISTING FIRE ALARM SYSTEM? | | | | | | 7) OK | | | | | | 8) PLEASE ILLUSTRATE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILING. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|