Plan Review Notes
Plan Review Notes For Permit 06050195
Permit Number 06050195
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-09-13 00:00:00***DENIED***
  
 SOME REVISIONS TO PLANS ARE NOTED
 HOWEVER SOME COMMENTS FROM PREVIOUS
 REVIEW NEED TO BE ACKNOWLEDGED.
  
 1) PLEASE DEFINE OCCUPANCY TYPE IN
 ACCORDANCE WITH FBC AND NFPA 101,
 CHAPTER 6 FOR ALL SPACES SHOWN ON PLANS.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION. PLEASE ADD TO PLANS.
  
 3) OK- REMOVED FROM PLANS.
  
 4) OK- REMOVED FROM PLANS.
  
 5) OK
  
 6) STROBES APPEAR TO HAVE BEEN REMOVED
 FROM INDIVIDUAL SPACES, BUT STILL ARE
 SHOWING IN CORRIDOR. AGAIN, PLEASE
 ADVISE WHAT STROBES ARE CONNECTED TO. IS
 THERE AN EXISTING FIRE ALARM SYSTEM?
  
 7) OK
  
 8) PLEASE ILLUSTRATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722