| 2006-09-07 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST COMPLY WITH THE MINIMUM REQUIREMENT |
| | OF 2/0 CU PER 250.66. |
| | |
| | 2} SEE ARTICLE 440-22 AND VERIFY THE OCP |
| | FOR THE ACU MEETS THESE PERAMETERS. ALL |
| | PANELS. |
| | |
| | 3} THERE IS NO PARKING LOT LIGHTING |
| | BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN |
| | THE HOUSE PANEL. PLEASE VERIFY AND |
| | INDICATE HOW LIT. |
| | |
| | 4} THE CIRCUITING FOR THE EMERGENCY WALL |
| | LIGHTS MUST BE CIRCUITED WITH THE MAIN |
| | LIGHTING IN THE AREA, SEE 700.12(5)(E). |
| | |
| | 5} PLEASE SUBMIT THE CORRECT ENERGY |
| | CALCULATION FORM AND INDICATE COMPLIANCE |
| | 13-414 AND 415 ON THE PLANS. SHOW |
| | OCCUPANCY SENSORS, TIMERS, ETC. |
| | |
| | 6} THE HOUSE PANEL DOES NOT HAVE |
| | CONTINUOUS LOADS IN THE CALCULATION PER 210.20(A). |
| | |
| | 7} THE ELECTRIC NOTE #1 REGARDING GFI('S |
| | IS INCORRECT @ 4'. SEE 210.8(A)(7). |
| | |
| | 8} ALL REFERENCES TO THE S.F.B.C., NOTES |
| | 4 AND 7, ARE OBSOLETE AND REFERENCES TO |
| | THAT CODE SHOULD BE REMOVED. |
| | |
| | 9} ELECTRICAL NOTE #8REGARDING 110.16 |
| | IS NOT TAKEN FROM THE 2002 NEC, AND DOES |
| | NOT PERTAIN TO DISCONNECTSWITCHES. |
| | THE FIRST 5 COMMENTS WERE ON THE |
| | PREVIOUS REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |