 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH THE MINIMUM REQUIREMENT
 OF 2/0 CU PER 250.66.
  
 2} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS.
  
 3} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 4} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E).
  
 5} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS. SHOW
 OCCUPANCY SENSORS, TIMERS, ETC.
  
 6} THE HOUSE PANEL DOES NOT HAVE
 CONTINUOUS LOADS IN THE CALCULATION PER 210.20(A).
  
 7} THE ELECTRIC NOTE #1 REGARDING GFI('S
 IS INCORRECT @ 4'. SEE 210.8(A)(7).
  
 8} ALL REFERENCES TO THE S.F.B.C., NOTES
 4 AND 7, ARE OBSOLETE AND REFERENCES TO
 THAT CODE SHOULD BE REMOVED.
  
 9} ELECTRICAL NOTE #8REGARDING 110.16
 IS NOT TAKEN FROM THE 2002 NEC, AND DOES
 NOT PERTAIN TO DISCONNECTSWITCHES.
 THE FIRST 5 COMMENTS WERE ON THE
 PREVIOUS REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  