Plan Review Notes
Plan Review Notes For Permit 06050195
Permit Number 06050195
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-15 00:00:00DENIED;
 1.OCCUPANCY TYPE NOT SHOWN ON PLANS.
 PLANS MUST COMPLY WITH FBC-2004 PLUMBING
 TABLE 403.1. DRINKING FOUNTAINS IN EACH
 SPACE ARE REQUIRED. IS AN EYE WASH
 REQUIRED AT SPRAY BOTH?
 2.WATER AND SANITARY RISER DIAGRAMS ARE
 REQUIRED. CHAPTER 1 WPB AMENDMENTS SEC.
 106.3.5.1.3(13).
 3.SHOW DETAIL OF HANDICAP BATHROOMS ON
 PLANSINCLUDE ALL REQUIRED MEASUREMENTS
 TO MEET FBC CHAPTER 11 SECS. 11-4.16 AND
 11-4.19.
 4.BACKFLOW PROTECTION REQUIRED ON WATER
 SERVICES.
 5. BUILDING DRAIN TO BE SIZEDUSING
 TABLE 710.1. SHOW MIN. SLOPE PER FOOT ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved