| Plan Review Notes For Permit 06050195 |
| Permit Number |
06050195 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-16 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE DEFINE OCCUPANCY TYPE IN | | | ACCORDANCE WITH FBC AND NFPA 101, | | | CHAPTER 6 FOR ALL SPACES SHOWN ON PLANS. | | | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 3) IF PAINT SPRAY BOOTH ISN'T EXISTING, | | | PLEASE NOTE THAT SEPARATE SHOP DRAWINGS | | | AND PERMIT ARE REQUIRED. AT THE TIME OF | | | PERMITTING, PLEASE INCLUDE MANUFACTURER | | | SPEC SHEETS. | | | | | | 4) PAINT SPRAY BOOTH TO BE INSTALLED IN | | | COMPLIANCE WITH NFPA 33. | | | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHERS | | | SHALL BE MOUNTED BASED ON THE HAZARD, | | | AND SHALL NOT EXCEED 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | 6) PLANS SHOW STROBES THROUGHOUT. WHAT | | | ARE THE STROBES CONNECTED TO? | | | | | | 7) ILLUMINATED EXIT SIGNS ARE REQUIRED | | | THAT WOULD LEAD PERSONS FROM SPACES 1-4 | | | INTO THE COMMON CORRIDOR. | | | | | | 8) PLEASE ILLUSTARTE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR WALLS AND | | | CEILINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|