| 2006-05-10 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST COMPLY WITH THE MINIMUM REQUIREMENT |
| | OF 2/0CU PER 250.66. |
| | |
| | 2} THE DISCONNECT ON THE RISER SAYS 475 |
| | AMP, THE LOAD CALCULATION SAYS 450 AMP |
| | SERVICE. PLEASE CORRELATE. |
| | |
| | 3} PLEASE INDICATE THE TYPE OF CONDUIT |
| | SPECIFIED FOR THE RISER AND SEE |
| | APPROPRIATE CHART IN CHAPTER #8 FOR |
| | CONDUIT FILL. #750 MCM THW IN A 2 1/2" |
| | CONDUIT IS NOT IN THE CHARTS. |
| | |
| | 4} INDICATE THE AMPERAGE RATING OF THE |
| | PANEL FEEDER DISCONNECTS IN THE METER |
| | CENTER, AND WHICH PANEL THEY FEED. |
| | |
| | 5} SEE ARTICLE 440-22 AND VERIFY THE OCP |
| | FOR THE ACU MEETS THESE PERAMETERS. ALL |
| | PANELS. |
| | |
| | 6} THERE IS NO PARKING LOT LIGHTING |
| | BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN |
| | THE HOUSE PANEL. PLEASE VERIFY AND |
| | INDICATE HOW LIT. |
| | |
| | 7} INDICATE MEANS OF EGRESS ILLUMINATION |
| | TO DIXIE HIGHWAY.( PLEASE SEE SHEET 1 |
| | REFERENCES "FEDERAL" HIGHWAY"). SEE |
| | 7.8.1.1 NFPA-101. |
| | |
| | 8} THE CIRCUITING FOR THE EMERGENCY WALL |
| | LIGHTS MUST BE CIRCUITED WITH THE MAIN |
| | LIGHTING IN THE AREA, SEE 700.12(5)(E). |
| | |
| | 8} PLEASE SUBMIT THE CORRECT ENERGY |
| | CALCULATION FORM AND INDICATE COMPLIANCE |
| | 13-414 AND 415 ON THE PLANS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |
| | |
| | |
| | |