 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH THE MINIMUM REQUIREMENT
 OF 2/0CU PER 250.66.
  
 2} THE DISCONNECT ON THE RISER SAYS 475
 AMP, THE LOAD CALCULATION SAYS 450 AMP
 SERVICE. PLEASE CORRELATE.
  
 3} PLEASE INDICATE THE TYPE OF CONDUIT
 SPECIFIED FOR THE RISER AND SEE
 APPROPRIATE CHART IN CHAPTER #8 FOR
 CONDUIT FILL. #750 MCM THW IN A 2 1/2"
 CONDUIT IS NOT IN THE CHARTS.
  
 4} INDICATE THE AMPERAGE RATING OF THE
 PANEL FEEDER DISCONNECTS IN THE METER
 CENTER, AND WHICH PANEL THEY FEED.
  
 5} SEE ARTICLE 440-22 AND VERIFY THE OCP
 FOR THE ACU MEETS THESE PERAMETERS. ALL
 PANELS.
  
 6} THERE IS NO PARKING LOT LIGHTING
 BRANCH CIRCUIT LISTED, OR TIME CLOCK, IN
 THE HOUSE PANEL. PLEASE VERIFY AND
 INDICATE HOW LIT.
  
 7} INDICATE MEANS OF EGRESS ILLUMINATION
 TO DIXIE HIGHWAY.( PLEASE SEE SHEET 1
 REFERENCES "FEDERAL" HIGHWAY"). SEE
 7.8.1.1 NFPA-101.
  
 8} THE CIRCUITING FOR THE EMERGENCY WALL
 LIGHTS MUST BE CIRCUITED WITH THE MAIN
 LIGHTING IN THE AREA, SEE 700.12(5)(E).
  
 8} PLEASE SUBMIT THE CORRECT ENERGY
 CALCULATION FORM AND INDICATE COMPLIANCE
 13-414 AND 415 ON THE PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  