Plan Review Notes
Plan Review Notes For Permit 06050181
Permit Number 06050181
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-04 00:00:00DENIED
  
 1) THE SYSTEM INDICATED ON THE NOA FOR
 MODIFIED BITUMEN ROOFING WILL REQUIRE
 ENHANCED FASTENING AT THE CORNERS AND
 PERIMETER AREAS. LIMITATION #7 ON PAGE
 20 OF THE NOA REQUIRES THE RAS 117
 CALCULATIONS TO DETERMINE FASTENER
 DENSITIES TO BE PREPARED, SIGNED AND
 SEALED BY AN ENGINEER, ARCHITECT OR
 REGISTERED ROOFING CONSULANT. SUBMIT
 SIGNED AND SEALED RAS 117 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  