| Plan Review Notes For Permit 06050177 |
| Permit Number |
06050177 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-05 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE PERSON TAKING RESPONSIBILITY FOR THE | | | DESIGN MUST PRINT AND SIGN THEIR NAME TO | | | SAME PER 106.3.4.2. FBC AS AMENDED. THIS | | | ARTICLE ALSO IS AN EXTRACTION FROM THE | | | EXEMPTION IN CHAPTER 471 OF THE FLORIDA | | | STATUTES , 471.003, ALLOWING YOU TO DRAW | | | YOUR OWN PLANS . | | | | | | IF USING 220.35 FOR CALCULATION THERE IS | | | NO 80%. PLEASE USE CODE ARTICLES WHEN | | | CALCULATING LOADS. 220 PART II, | | | 220.31(B)- AHU AT 100%. ONLY THE | | | CIRCUITS IN THE GENERATOR PANEL NEED BE | | | CALCULATED. | | | | | | PLEASE LOCATE ALL SERVICE EQUIPMENT ON | | | THE PLAN, METER ENCLOSURE, | | | DISCONNECTS,ATS, GENERATOR AND PANELS, | | | SO THAT COMPLIANCE WITH ARTICLES 225 AND | | | 230 CAN BE REVIEWED. ASITE PLAN WILL | | | SUFFICE. | | | | | | SUBMIT MANUFACTURERS SPEC'S FOR THE ATS, | | | MUST BE SERVICE RATED OR HAVE A | | | DISCONNECTING MEANS FROM THE GENERATOR. | | | ARTICLE 225.31-225.38. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | | | | | | | |
|