Date Text
2006-06-05 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2. FBC AS AMENDED. THIS
 ARTICLE ALSO IS AN EXTRACTION FROM THE
 EXEMPTION IN CHAPTER 471 OF THE FLORIDA
 STATUTES , 471.003, ALLOWING YOU TO DRAW
 YOUR OWN PLANS .
  
 IF USING 220.35 FOR CALCULATION THERE IS
 NO 80%. PLEASE USE CODE ARTICLES WHEN
 CALCULATING LOADS. 220 PART II,
 220.31(B)- AHU AT 100%. ONLY THE
 CIRCUITS IN THE GENERATOR PANEL NEED BE
 CALCULATED.
  
 PLEASE LOCATE ALL SERVICE EQUIPMENT ON
 THE PLAN, METER ENCLOSURE,
 DISCONNECTS,ATS, GENERATOR AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED. ASITE PLAN WILL
 SUFFICE.
  
 SUBMIT MANUFACTURERS SPEC'S FOR THE ATS,
 MUST BE SERVICE RATED OR HAVE A
 DISCONNECTING MEANS FROM THE GENERATOR.
 ARTICLE 225.31-225.38.
  