| Plan Review Notes For Permit 06050166 |
| Permit Number |
06050166 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-30 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} SMOKE DETECTORS MUST BE INSTALLED TO | | | COMPLY WITH R313.1 RESIDENTIAL FLORIDA | | | BUILDING CODE. | | | | | | 2} INDICATE COMPLIANCE WITH ARTICLE | | | 250.50 FOR THE GROUNDING ELECTRODE | | | SYSTEM. ALL AVAILABLE MUST BE USED ON | | | THE RISER. SEE 250.52(A)(3) FOR FOOTER | | | STEEL. | | | | | | 3} THE 7000 WATT HEAT STRIPS ARE | | | CALCULATED AT 5700 WATTS. PLEASE CORRECT | | | THE CALCULATION. | | | | | | 4} THE GARAGE RECEPTACLES MUST BE GFI | | | PROTECTED PER 210.52(G). | | | | | | 5} TWO SETS OF PLANS ARE REQUIRED FOR | | | REVIEW PER 106.1 FBC. ONLY ONE SHEET 4.5 | | | WAS SUBMITTED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|