Plan Review Notes
Plan Review Notes For Permit 06050166
Permit Number 06050166
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-30 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 2} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SEE 250.52(A)(3) FOR FOOTER
 STEEL.
  
 3} THE 7000 WATT HEAT STRIPS ARE
 CALCULATED AT 5700 WATTS. PLEASE CORRECT
 THE CALCULATION.
  
 4} THE GARAGE RECEPTACLES MUST BE GFI
 PROTECTED PER 210.52(G).
  
 5} TWO SETS OF PLANS ARE REQUIRED FOR
 REVIEW PER 106.1 FBC. ONLY ONE SHEET 4.5
 WAS SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  