2006-05-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED
 ON THE DRAWING AND TO THE PLUMBING NOTES
 FOR PLUMBING PLAN REVIEW:
  
 1.PER CHAPTER 1, SECTION 106, PLEASE
 SUBMIT A DRAWING INDICATING EXISTING
 FLOOR PLAN LAY-OUT OF ROOMS AND A
 SEPERATE DRAWING INDICATING THE NEW
 PROPOSED FLOOR PLAN LAY-OUT.
 2. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL. NOTE THE SANITARY
 ISOMETRIC RISER DIAGRAM ON SHEET E-1
 DOES NOT REFLECT THE FLOOR PLAN.
 (A) SHOWER IS NOT INDICATED ON SANI-
 TARY RISER DIAGRAM.
 3. THE SINK INDICATED ON THE SANITARY
 PLUMBING RISER DIAGRAM IS NOT VENTED PER
 SECTION 901.2.1. PLEASE CORRECT FOR
 RESUBMITTAL.
 4. PLUMBING NOTES #12 AND #14 ON SHEET
 E-1 ARE INCORRECT. #12 SHOULD READ,
 SOIL, WASTE & VENTING TO BE PVC DWV NOT
 DVW, PLEASE CORRECT FOR RESUBMITTAL. #14
 SHOULD READ WATER HAMMER ARRESTORS NOT
 AIR HANDLER ARRESTERS PLEASE CORRECT FOR
 RESUBMITTAL
  
 END OF COMMENTS:
  