| Plan Review Notes For Permit 06050125 |
| Permit Number |
06050125 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-06-05 00:00:00 | DENIED; | | | 1.DELETE WATER HEATER DETAIL HEATER IS | | | GAS NOT ELECTRIC. GAS HEATER TO BE 18" | | | AFF TO GAS BURNERS. | | | 2.P & T RELIEF VALVE REQUIRES AN AIR GAP | | | FITTING IF RUN TO OUTSIDE FBC-2004 | | | PLUMBING SEC. 504.6.1. | | | 3.CLEANOUT REQUIRED ON W/M STACK AT 48" | | | AFF. | | | 4.WATER HEATER CLOSET OUTSIDE AIR | | | REQUIRED AT THE TOP OF THE W/H ROOM | | | ALSO, SEE MECHANICAL CODE SEC. 702 AND | | | 703.2. | | | 5.CLOTHES DRYER IS IN A CONFINED SPACE, | | | SEE SEC. 702. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|