Plan Review Notes
Plan Review Notes For Permit 06050125
Permit Number 06050125
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-31 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} THERE ARE NO RATINGS ON ANY OF THE
 PROPOSED SERVICE EQUIPMENT. INDICATE
 VOLTAGE , AMPERE AND MAIN BREAKER
 RATINGS.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 3} PROVIDE PANEL SCHEDULES FOR ALL
 PANELS. 215.5.
  
 4} PROVIDE A TOTAL LOAD CALCULATION PER
 220 PART II, OR OPTIONAL PER 220.III.
 INDICATE WHICH ARTICLE IS BEING USED.
 THE CALCULATION GIVEN IS ONLY PARTIAL.
  
 5} THE DESCRIPTION ON THE APPLICATION
 DOES NOT MENTION THE INTERIOR WORK,
 INCLUDING AN ELECTRICAL SERVICE CHANGE
 AND BRANCH CIRCUIT WIRING. PLEASE
 INDICATE THE SCOPE OF WORK ON THE
 APPLICATION.
  