| Plan Review Notes For Permit 06050125 |
| Permit Number |
06050125 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-31 00:00:00 | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} THERE ARE NO RATINGS ON ANY OF THE | | | PROPOSED SERVICE EQUIPMENT. INDICATE | | | VOLTAGE , AMPERE AND MAIN BREAKER | | | RATINGS. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT | | | ON THE PLAN, METER ENCLOSURE, | | | DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | | BE REVIEWED. | | | | | | 3} PROVIDE PANEL SCHEDULES FOR ALL | | | PANELS. 215.5. | | | | | | 4} PROVIDE A TOTAL LOAD CALCULATION PER | | | 220 PART II, OR OPTIONAL PER 220.III. | | | INDICATE WHICH ARTICLE IS BEING USED. | | | THE CALCULATION GIVEN IS ONLY PARTIAL. | | | | | | 5} THE DESCRIPTION ON THE APPLICATION | | | DOES NOT MENTION THE INTERIOR WORK, | | | INCLUDING AN ELECTRICAL SERVICE CHANGE | | | AND BRANCH CIRCUIT WIRING. PLEASE | | | INDICATE THE SCOPE OF WORK ON THE | | | APPLICATION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected]. | | | | | | | | | |
|