| Plan Review Notes For Permit 06050117 |
| Permit Number |
06050117 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-05-22 00:00:00 | DENIED | | | | | | 1) ENHANCED FASTENING OF THE ANCHOR | | | SHEET IS REQUIRED TO OBTAIN THE REQUIRED | | | UPLIFT PRESSURES AT THE PERIMETER AND | | | CORNER AREAS FOR THE TAMKO MODIFIED | | | SYSTEM THAT YOU INDICATED ON THE NOA. | | | LIMITATION #7 FROM THE NOA REQUIRES THAT | | | THE RAS 117 CALCULATIONS TO DETERMINE | | | THE FASTENER DENSITIES BE PREPARED, | | | SIGNED AND SEALED BY AN ARCHITECT, | | | ENGINEER OR A REGISTERED ROOF | | | CONSULTANT. SUBMIT SIGNED AND SEALED | | | RAS 117 CALCULATIONS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|