| 2006-05-02 00:00:00 | DENIED |
| | |
| | 1) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | COVERSHEET WITH FL PRODUCT NUMBER FOR |
| | ALL PRODUCTS. |
| | |
| | 2) INDICATE WHICH ONE OF THE APPROVED |
| | SYSTEMS LISTED IN NOA THE FOR THE |
| | MODIFIED BITUMEN ROOF SYSTEM WILL BE |
| | INSTALLED. CIRCLE THE APPROVED ASSEMBLY |
| | INFORMATION IN THE NOA ON PAGES 31-38 |
| | FOR NON-INSULATED WOOD DECKS. NOTE: NONE |
| | OF THE SYSTEMS LISTED WILL WORK WITHOUT |
| | ENHANCED FASTENING, WHICH IS ALLOWED BY |
| | LIMITATION #7 ON PAGE 40 OF THE NOA. |
| | HOWEVER, LIMITATION #7 REQUIRES THE RAS |
| | 117 CALCULATIONS FOR INCREASED FASTENERS |
| | DENSITIES BEPREPARED BY AN ENGINEER, |
| | ARCHITECT OR REGISTERED ROOFING |
| | CONSULTANT. THEREFORE, SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | 3) SUBMIT PRODUCT APPROVALS FOR THE |
| | ASPHALT SHINGLES. THE PRODUCT APPROVAL |
| | THAT WAS SUBMITTED IS FOR HIP AND RIDGE |
| | CAP SHINGLES. |
| | |
| | 4) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |