| Plan Review Notes For Permit 06050052 |
| Permit Number |
06050052 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-06-28 00:00:00 | REVISION: CHANGED PIPING FROM CSST TO | | | GALVANIZED, DELETED FUTURE BBQ. | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 900 CUBIC FEET REQUIRED. | | | | | | IF WATER HEATER ROOM IS A CONFINED | | | SPACE, OPENINGS REQUIRED PER SECTION | | | 304.5 OR SECTION 304.6 SHALL BE | | | INSTALLED. | | | MINIMUM 9,950 CUBIC FEET REQUIRED. |
|