Plan Review Notes
Plan Review Notes For Permit 06050021
Permit Number 06050021
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-09 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE INFORMATION REQUIRED
 ON TITLE BLOCKS PER FS 481.219,471.023
 PLEASE SEE MEP SHEETS APPEAR TO CONTAIN
 AN ENGINEERING BUSINESS LICENSE NUMBER
 STAMPED ON PLANS WHICH IS OK, HOWEVER
 PLEASE SEE "A" SHEETS SHICH DO NOT
 CONTAIN THE PRINTED NAME AND LICENSE
 NUMBER OF SAID ARCHITECT.
 PLEASE ALSO SEE OF THE FIRM IS
 PRACTICING ARCHITECTURE, THEN A FIRM
 LICENSE NUMBER IS ALSO REQUIRED FOR THE
 ARCH FIRM.
 FS 481.219,FLORIDA ADMINISTRATIVE CODE
 61G1-16.004.
 PLEASE SEE MEP SHEETS SHALL ALSO CONTAIN
 THIS CERTIFICATE OF AUTHORIZATION #.
 THIS COMMENT IS FOR ALL SHEETS AND ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE THIS JOB AND SCOPE
 OF WORK ONLY REQUIRES TWO SETS OF PLANS
 TO BE SUBMITTED. PLEASE SEESIX SETS
 WERE SUBMITTED WHERE ONLY TWO ARE NEEDED
 BUT UP TO THREE SETS MAY BE SUBMITTED
 AND UP TO THREE WILL BE STAMPED.
  
  
 3) NOTE: PLEASE SEE 2004 FBC CHAPTER 13,
 13-413.1ABC.1 FOR VOLTAGE DROP.
 PLEASE SEE LIGHTING CONTROLS REQUIRED
 PER 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE SEE CALCULATIONS FOR RENOVATIONS
 13-415.1.AB.1
 PLEASE SEE 13-415.1.ABC.3
 ETC.
  
 4) NOTE: PLEASE CLARIFY SERVICE AND
 WHERE FEED IS COMING FROM. IS NEW METER
 BEING FED FROM AN EXISTING
 GUTTER?SERVICE? ETC. PLEASE KNOW,
 LOCATION WILL NEED TO BE VERIFIED.
 230.70,230.72, 230.2 ETC
 PLEASE VERIFY AND INDICATE IF ADDING
 LOADS TO AN EXISTING SERVICE.
  
 5) NOTE: PLEASE SEE THE FOLLOWING CODES
 SHALL BE REFLECTED ON SAID PLANS AT A
 MIN.
 NFPA-101 2003, NFPA-72 2002, NFPA-70
 2002.
  
 6) NOTE: PLEASE VERIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 ** THIS IS VERY IMPORTNANT**
 WHEN RESUBMITTING PLANS ONCE ALL REVIEWS
 ARE DONE AND CORRECTIONS ARE MADE,
 PLEASE COMPLETELY REMOVE AND AND ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. ONLY ONE
 COPY OF THE OLD/VOIDED SHEETS SHOUDL
 ACCOMPANY THE NEW SETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  