| Plan Review Notes For Permit 06050011 |
| Permit Number |
06050011 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-08 00:00:00 | ******DENIED****** | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR PLAN REVIEW FOR A GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS.(NOTE: I HAVE ENCLOSED AN | | | ISOMETRIC DRAWING OF THE SUBMITTED | | | PERMIT APPLICATION NEEDED FOR PLAN | | | REVIEW YOU NEED TO FILL IN THE | | | INFORMATION WHERE THE RED X'S ARE | | | INDICATED) | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING | | | USED.(NOTE:ON THE SAMPLE ISOMETRIC | | | DRAWING THE RED X'S INDICATE WHERE THIS | | | INFORMATION LACKING AND NEEDED FOR PLAN | | | REVIEW) | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3).(NOTE: NEED TO | | | KNOW THE LONGEST LENGTH) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | | | | |
|