| Plan Review Notes For Permit 06050004 |
| Permit Number |
06050004 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-07-25 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | FROM PREVIOUS LISTS: | | | | | | _XX_4.COMPLETE THE ATTACHED | | | INSTALLATION SCHEDULE OR PROVIDE | | | REQUIRED INFORMATION IN A SIMILAR | | | FORMAT.YOU MAY SHOW ANCHOR SPACING BY | | | CIRCLING IT ON THE APPROPRIATE CHARTS ON | | | THE PRODUCT APPROVAL.PLEASE USE INK | | | RATHER THAN HIGHLIGHTER. | | | | | | 2ND REVIEW - SPECIFY ANCHORING.YOU | | | HAVE CIRCLED THE CHART; THIS DOES NOT | | | SHOW CODE COMPLIANCE, ANCHOR SPACING | | | REQUIRED FOR PERMITTING. | | | | | | 3RD REVIEW - THE INSTALLATION SCHEDULE | | | WHICH YOU HAVE USED IS NONCOMPLIANT.IT | | | REFERS TO ASCE7-98 WIND LOAD (PSF).YOU | | | HAVE PUT "140" IN THAT COLUMN.THIS IS | | | THE WIND SPEED, NOT THE WIND LOAD.THE | | | CORRECT REFERENCE IS ASCE7-02, FBC35. | | | | | | YOU HAVE INDICATED THAT THERE IS A 1/3 | | | ALLOWABLE STRESS INCREASE.THIS IS NOT | | | ALLOWED, FBC 1605.3.1.1(2). | | | | | | THE ANCHORING SPECIFIED, 9", IS NOT | | | COMPLIANT FOR THE SPAN IN MASONRY | | | SUBSTRATE. | | | |
|