| Notes |
| Date |
Text |
| 2006-05-04 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE COMPLETE THE CODE SUMMARY ON | | | SHEET 1.1. ALSO NOTE THAT THE REFERENCE | | | TO THE "ELECTRICAL CODE BEING THE | | | "LATEST EDITION " IS INCORRECT AS TH | | | ESTATE OF FLORIDA IS CURRENTLY ENFORCING | | | THE LAST ADOPTED EDITION WHICH IS 2002. | | | THE CURRENT EDITION IS 2005. | | | | | | 2} PROVIDE A LOAD CALCULATION PER | | | ARTICLE 220 2002 NEC, INDICATE THE SIZE | | | OF THE BUILDING SERVICE, AND SHOW THE | | | CALCULATION FOR THIS PROJECT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | | | | | | |
|