| 2006-08-07 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA STATUTES |
| | |
| | THE FOLLOWING INFORMATION IS STILL |
| | REQUIRED FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. THE ISOMETRIC SANITARY PLUMBING RISER |
| | DIAGRAM ON SHEET 6 OF 6 STILL DOES NOT |
| | REFLECT THE FLOOR PLAN. THE TUB AND |
| | DOUBLE BOWL SINK ARE INDICATED WRONG PER |
| | THE FLOOR PLAN LAYOUT. PLEASE SEE |
| | CORRECTED SANITARY ISOMETRIC PLUMBING |
| | RISER DIAGRAM IN RED INK FOR REFERENCE |
| | FOR RESUBMITTAL. |
| | 2. ALL PIPES AND TRAPS MUST BE SIZED PER |
| | FBC-2004, CHAPTER 1, SECTION 106.3.5.4. |
| | PLEASE REFERENCE CORRECTED PLMG. RISER |
| | ON SHEET 6 OF 6 FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | 3. PLEASE SEE ELECTRICAL COMMENT #4 |
| | STATE STATUTE 471.025 ENGINEER OF RECORD |
| | MUST SIGN, SEAL AND DATE DOCUMENTS. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |