Plan Review Notes
Plan Review Notes For Permit 06041252
Permit Number 06041252
Review Stop P
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
  
 1. THE ISOMETRIC SANITARY PLUMBING RISER
 DIAGRAM ON SHEET 6 OF 6 STILL DOES NOT
 REFLECT THE FLOOR PLAN. THE TUB AND
 DOUBLE BOWL SINK ARE INDICATED WRONG PER
 THE FLOOR PLAN LAYOUT. PLEASE SEE
 CORRECTED SANITARY ISOMETRIC PLUMBING
 RISER DIAGRAM IN RED INK FOR REFERENCE
 FOR RESUBMITTAL.
 2. ALL PIPES AND TRAPS MUST BE SIZED PER
 FBC-2004, CHAPTER 1, SECTION 106.3.5.4.
 PLEASE REFERENCE CORRECTED PLMG. RISER
 ON SHEET 6 OF 6 FOR REFERENCE FOR
 RESUBMITTAL.
 3. PLEASE SEE ELECTRICAL COMMENT #4
 STATE STATUTE 471.025 ENGINEER OF RECORD
 MUST SIGN, SEAL AND DATE DOCUMENTS.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  