| 2006-08-07 00:00:00 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} A GROUNDING ELECTRODE CONDUCTOR IS | | | REQUIRED AT THE SEPARATE STRUCTURE PER | | | 250.32, SIZED PER 250.66. | | | | | | 2} BATH CIRCUIT REQUIRED TO HAVE A 20 | | | AMP RECEPTACLE PER 210.11(C)(3), LOCATED | | | PER 210.52(D), AND BE GFI PROTECTED PER | | | 210.8(A)(1).INDICATE COMPLIANCE ON THE | | | PLAN AND IN THE PANEL SCXHEDULE. | | | | | | 3} THE "MINI SPLIT A/C UNIT" ON THE PLAN | | | IS NOT IN THE PANEL SCHEDULE. ALSO | | | VERIFY THE SPECIFICATIONS IN THE | | | CALCULATION. (10K)? | | | | | | 4} THE ENGINEER OF RECORD MUST SIGN, | | | SEAL AND DATE THE DOCUMENTS PER 471.025 | | | FLORIDA STATUTES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | |
|