Plan Review Notes
Plan Review Notes For Permit 06041252
Permit Number 06041252
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A GROUNDING ELECTRODE CONDUCTOR IS
 REQUIRED AT THE SEPARATE STRUCTURE PER
 250.32, SIZED PER 250.66.
  
 2} BATH CIRCUIT REQUIRED TO HAVE A 20
 AMP RECEPTACLE PER 210.11(C)(3), LOCATED
 PER 210.52(D), AND BE GFI PROTECTED PER
 210.8(A)(1).INDICATE COMPLIANCE ON THE
 PLAN AND IN THE PANEL SCXHEDULE.
  
 3} THE "MINI SPLIT A/C UNIT" ON THE PLAN
 IS NOT IN THE PANEL SCHEDULE. ALSO
 VERIFY THE SPECIFICATIONS IN THE
 CALCULATION. (10K)?
  
 4} THE ENGINEER OF RECORD MUST SIGN,
 SEAL AND DATE THE DOCUMENTS PER 471.025
 FLORIDA STATUTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  