Plan Review Notes
Plan Review Notes For Permit 06041252
Permit Number 06041252
Review Stop P
Sequence Number 1
Notes
Date Text
2006-05-24 00:00:00******DENIED******
 REFERENCE:FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW FOR A PERMIT:
  
 1. THE SANITARY PLUMBING ISOMETRIC RISER
 DIAGRAM ON SHEET D3 DOES NOT REFLECT THE
 FLOOR PLAN ON SHEET F1. THE FOLLOWING
 ARE MINIMUM REQUIREMENTS FOR THE
 SANITARY PLUMBING ISOMETRIC RISER
 DIAGRAM.
 (A) 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.(NOTE: PIPE SIZES NOT
 INDICATED FOR THE TUB, LAV, W/C, AND
 SINK IN WET BAR IS MIS LABELED LAV AND
 BOTH BOWLS OF SINK NEED TO BE INDICATED
 AND SIZED. PLEASE REFERENCE CORRECTED
 DRAWING ON SHEET D3 FOR RESUBMITTAL.)
 2. THE FOLLOWING ARE REQUIREMENTS FOR
 CLEANOUT LOCATIONS ON THE PLBG. SANITARY
 ISO. RISER DIAGRAM. PLEASE REFERENCE
 CORRECTED DRAWING ON SHEET D3 FOR
 RESUBMITTAL.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 3. THE TUB INDICATED ON SHEET D3
 SANITARY PLBG. ISO. RISER DIAGRAM IS NOT
 VENTED PER SECTION 901.2.1.
 4. SEE EXAMPLE OF PLBG. ISO. RISER
 DIAGRAM THAT MEETS CODE ATTACHED TO PLBG
 COMMENTS FOR RESUBMITTAL REFERENCE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  