| Plan Review Notes For Permit 06041193 |
| Permit Number |
06041193 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-10-18 15:47:59 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT (1) IN REFERENCE TO | | | FUEL SUPPLY REQUIREMENTS IN ACCORDANCE WITH NFPA 20. | | | | | | 2) WORK SHALL COMPLY WITH NFPA 110. PLEASE PROVIDE | | | ACKNOWLEDGEMENT AS THIS COMMENT IS FROM THE FIRST FIRE | | | REVIEW. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 |
|