| 2006-09-15 00:00:00 | **** UNSAT 2ND REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE PROPOSED |
| | 250 GAL SUB BASE FUEL TANK DOES NOT MEET |
| | THE MIN REQUIRED FOR 8HRS OF OPERATION |
| | REQUIRED FOR FIRE PUMP AND ALL OTHER |
| | REQUIRED SYSTEMS FOR THEIR LOADS AT |
| | 100%. |
| | PLEASE SEE NFPA-20 6.2.2 |
| | THE FUEL SUPPLY CAPACITY SHALL BE |
| | SUFFICIENT TO PROVIDE 8 HOURS OF FIRE |
| | PUMP OPERATION AT 100 PERCENT OF THE |
| | RATED PUMP CAPACITY IN ADDITION TO THE |
| | SUPPLY REQUIRED FOR OTHER DEMANDS. |
| | |
| | 2) NOTE: PLEASE SEE THAT THIS IS A |
| | "THRESHOLD" PROJECT AND THREE SETS OF |
| | PLANS AND ALL SUBMITTIALS ARE REQUIRED |
| | FOR REVIEW AND STAMPING. 2001 FBC |
| | 104.2.1, 104.2.1.2 ADIMINISTRATIVE |
| | SECTION AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH. |
| | |
| | ** PLEASE SEE THIS WAS NOTED ON PREVIOUS |
| | REVIEW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |