Plan Review Notes
Plan Review Notes For Permit 06041184
Permit Number 06041184
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-13 15:42:24 
  
  
 ******REVISION DENIED******
  
 1)UNDER ENGINEERS FINDINGS (NOTE C) THE STEEL STUD
 HAS A 33 KSI STEEL YIELD STRENGTH BUT THE STRUCTURAL
 DRAWING S/1 AND THE FLORIDA STATEWIDE PRODUCT APPROVAL
 BOTH STATE A MINIMUM OF36 KSI IA REQUIRED.
  
 2)ENGINEER SHEET S/1 IS FOR A CHANGE IN FASTENER TYPE
 FROM THE PRODUCT APPROVAL FL# 5337 AND AS SUCH REQUIRES
 THE ENGINEER OF RECORDS STATEMENT THAT THE NEW FASTENER
 MEETS OR EXCEEDS THE ORIGINAL FASTENERS. CONCLUSIONS
 ONLY STATE THAT THE NUAIR SERIES 9000 WINDOWS WHEN
 ATTACHED TO THE EXISTING STRUCTURE IS SUBSTANTIALLY
 EQUIVALENT.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716