| Plan Review Notes For Permit 06041184 |
| Permit Number |
06041184 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-06-13 15:42:24 | | | | | | | | | | ******REVISION DENIED****** | | | | | | 1)UNDER ENGINEERS FINDINGS (NOTE C) THE STEEL STUD | | | HAS A 33 KSI STEEL YIELD STRENGTH BUT THE STRUCTURAL | | | DRAWING S/1 AND THE FLORIDA STATEWIDE PRODUCT APPROVAL | | | BOTH STATE A MINIMUM OF36 KSI IA REQUIRED. | | | | | | 2)ENGINEER SHEET S/1 IS FOR A CHANGE IN FASTENER TYPE | | | FROM THE PRODUCT APPROVAL FL# 5337 AND AS SUCH REQUIRES | | | THE ENGINEER OF RECORDS STATEMENT THAT THE NEW FASTENER | | | MEETS OR EXCEEDS THE ORIGINAL FASTENERS. CONCLUSIONS | | | ONLY STATE THAT THE NUAIR SERIES 9000 WINDOWS WHEN | | | ATTACHED TO THE EXISTING STRUCTURE IS SUBSTANTIALLY | | | EQUIVALENT. | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|