2006-08-31 00:00:00COMMENTS REGARDING THE ENGINEERING
 LETTER:
  
 1.)ENGINEERING LETTERS ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS, TWO
 ORIGINALS REQUIRED.THE LETTER
 SUBMITTED VIA FAX FOR PRELIMINARY WAS
 ONE PAGE WITH NO SIGNATURE OR SEAL.WAS
 THE LETTER COMPLETE?
  
 2.)THE LETTER IS TO REFER TO THE
 SPECIFIC PRODUCT BEING INSTALLED.IT IS
 NOT CLEAR FROM THE LETTER WHICH PRODUCT
 WAS REVIEWED.
  
 3.)ENGINEERING IS TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
  
2006-08-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE WINDOW PRODUCT APPROVALS
 SUBMITTED APPEAR CODE COMPLIANT.
 HOWEVER, THE FLOOR PLAN SUBMITTED
 PREVIOUSLY SHOWS 3 MULLIONS.ONE IS A
 90 DEGREE MULLION.IS THIS CORRECT?IF
 IT IS, SUBMIT A MULLION PRODUCT APPROVAL
 FOR THIS APPLICATION.IF NOT, REVISE
 THE FLOOR PLAN TO CORRECTLY REFLECT THE
 SCOPE OF WORK.MAKE ALL NOTES ON THE
 FLOOR PLAN LEGIBLE; THE MULLION NOTE IS
 VERY SMALL AND IT IS DIFFICULT TO READ
 THE WINDOW SIZES.
  
 2.)THE MULLION PRODUCT APPROVAL
 APPEARS TO BE LIMITED TO SIMONTON
 STORMBREAKER WINDOWS.SUBMIT A MULLION
 PRODUCT APPROVAL.